8-2 AC OUTPUT MEASURING
TO
Use a circuit like the one shown in Fig.
|
| I |
|
|
|
|
|
| I | 240v |
Rated | voltage | 1 | 11ov | I | 12OV | 220 | v | 230v | 1 | |
Voltage | range | ! |
|
| 118%125V | 218 - | 225 V | 228 - 235 V | 238 | - 245 V |
Table 8- 1
8-3 DC OUTPUT MEASURING
00
SWITCH
LOAD
@
@
DC TERMINAL
Fig.
Switch the power on, when 1.45R resistance attached as a load, check that the voltage is within the range of 13 to 11V.
NOTE: If a battery is connected as the load, the output voltage increases by about I to ZV, possibly causing battery over- charge. Control battery liquid level during charging to prevent overcharging.
84 MEASURING INSULATION RESISTANCE
Connect amegger tester to one of the two receptable output terminals and the ground terminal, then measure the insula- tion resistance. An insulation resistance of 1 megohms or more is normal. (The original insulation resistance at the time of shipment from the factory is 10 megohms or more.) If it is less than 1 megohm, disassemble the generator and measure the insulation resistance of the stator, rotor and control box individually.
Fig.