Liebert 350VA to 1000VA Environmental Conditions, User Accessories and Packaging Warranty

Page 4

F.Voltage Transient Response: ±15% in Normal mode for 0-100-0% loading of the UPS rating, ±5% in Battery mode for 20-100-20% loading of the UPS rating.

G.Transient Recovery Time: To within ±8% of nominal voltage in < 2 cycles.

H.Efficiency: >95% (Normal mode)

>90% (Buck/Boost mode)

I.Output Power Cords: The 230 VAC units have two (2) detachable IEC-320-C14 output power cords measuring 2m (6.6 ft) in length.

1.4ENVIRONMENTAL CONDITIONS

A.Ambient Temperature

Operating: 32oF ─ 104oF (0oC ─ 40oC) for altitudes 0 ─ 5,000 ft. (0 ─ 1500 meters) above sea level

32°F ─ 86°F (0°C ─ 30°C) for altitudes 5000 ft ─ 10,000 ft (1500 ─ 3000 meters) above sea level.

77o F (25oC) for optimum battery performance

Storage: 5°F ─ 104°F (-15°C ─ 40°C) with batteries 5oF ─ 122oF (-15oC ─ 50oC) without batteries

68oF (20oC) for optimum battery storage.

B. Relative Humidity

0─ 95% non-condensing. C. Altitude:

3,000 m (10,000 ft. max.), without power derating when operated within the temperature specified in section 1.4.A.

D. Audible Noise

Noise generated by the UPS during normal operation does not exceed 40dB when measured at 1 meter from the surface of the UPS, “A” weighted.

E. Electrostatic Discharge

The 120 VAC units are able to withstand an electrostatic discharge compliant to EN61000-4-2, level 3, Criteria A without damage and without affecting the connected load. The 230 VAC units are able to withstand an electrostatic discharge compliant to EN61000-4-2, level 3, Criteria A without damage and without affecting the connected load.

1.5USER ACCESSORIES AND PACKAGING

The specified UPS system is supplied with one (1) user's manual. The manual includes installation drawings and instructions, a functional description of the equipment, safety precautions, illustrations, operating procedures, and general maintenance guidelines. The UPS is also supplied with one (1) Multilink™ software CD, one (1) Multilink serial cable (10-ft; 3m), one (1) USB cable (6-ft; 1.8m), one (1) RJ-11 cord (7-ft; 2.1m) and one (1) warranty card (120V models only). The package of the 230 VAC units also includes two (2) output power cords (2m; 6.6 ft). The package meets the requirements of ISTA Procedure 1A.

1.6WARRANTY

The manufacturer warrants the UPS against defects in materials and workmanship for two (2) years. The warranty covers all parts. An optional one (1) or three (3) year extended warranty is available from the manufacturer.

PowerSure PSA

4

Guide Specification

350 – 1000VA

 

SL-23271 8/03

Image 4
Contents General Summary StandardsSystem Description Modes of OperationOutput Design RequirementsPerformance Requirements 1.3.3.1 AC Input to UPS AC Output Voltage Configuration Voltage Regulation ±10% steady stateUser Accessories and Packaging Warranty Environmental ConditionsUnit Unit Dimensions VAC Units WeightQuality Assurance Product FabricationBattery Recharge Battery Over-Discharge ProtectionBi-Directional Converter 2.2.2.1 General Bi-Directional Converter DC ProtectionUnit VAC Units Communications