Liebert 350VA to 1000VA Quality Assurance, Product Fabrication, Unit Unit Dimensions VAC Units

Page 5

1.7QUALITY ASSURANCE

1.7.1Manufacturer Qualifications

Liebert Corporation provides more than twenty years experience in the design, manufacture, and testing of solid-state UPS systems and the company is certified to ISO 9001.

1.7.2Factory Testing

Before shipment, the product is tested to assure compliance with the specification.

2.0PRODUCT

2.1FABRICATION

All materials and components making up the UPS are new, of current manufacture, and have not been in prior service except as required during factory testing. All relays are provided with dust covers.

2.1.2Wiring

Wiring practices, materials, and coding are in accordance with the requirements of the standards listed in section 1.2. All wiring is copper.

2.1.3Cabinet

The UPS unit comprised of: TVSS & EMI/RFI Filters, Bi-Directional Converter, Automatic Voltage Regulator and Battery consisting of the appropriate number of sealed battery cells; is housed in a mini-tower NEMA type 1 enclosure. The UPS cabinet is injection-molded standard color. Dimensions and weights are:

UNIT

UNIT DIMENSIONS

120 VAC UNITS

230 VAC UNITS

 

W x D x H in (mm)

WEIGHT

WEIGHT

 

lbs

(kg)

kg (lbs)

 

 

 

350VA

4.6 x 7.7 x 8.7

(116 x 196 x 222)

16.8

(7.6)

7 (15.4)

500VA

4.6 x 7.7 x 8.7

(116 x 196 x 222)

17.2

(7.8)

7.4 (16.3)

650VA

4.6 x 14.1 x 8.7

(116 x 358 x 222)

20.7

(9.4)

9.1 (20.1)

1000VA

4.6 x 14.1 x 8.7

(116 x 358 x 222)

29.7

(13.5)

13.2 (19.1)

2.1.4Cooling

The UPS is convection cooled.

2.2COMPONENTS AND OPERATION

2.2.1Input Protection

The UPS has built-in protection against undervoltage, overcurrent, and overvoltage conditions including low-energy lightning surges introduced on the primary input power source. The UPS is provided with an input circuit protector. The 120 VAC UPS models withstand input surges without damage per criteria listed in IEEE C62.41, Category A, Level 3 and the 230 VAC UPS models withstand input surges without damage per criteria listed in EN61000-4-5, Level 3, Criteria A. Additionally, the UPS is supplied with one pair of Data Line Protection Connectors to provide phone, fax or modem line surge protection via RJ-45 connectors. These Data Line Protection Connectors provide transmission for 10/100 Base-T Ethernet connection.

PowerSure PSA

5

Guide Specification

350 – 1000VA

 

SL-23271 8/03

Image 5
Contents Standards General SummarySystem Description Modes of OperationPerformance Requirements 1.3.3.1 AC Input to UPS Design RequirementsOutput Voltage Regulation ±10% steady state AC Output Voltage ConfigurationEnvironmental Conditions User Accessories and Packaging WarrantyWeight Unit Unit Dimensions VAC UnitsQuality Assurance Product FabricationBattery Over-Discharge Protection Battery RechargeBi-Directional Converter 2.2.2.1 General Bi-Directional Converter DC ProtectionUnit VAC Units Communications