Installation 46
Installing the Power Cord
Installation of the power cord must be done by a qualified electrician and in accordance with local
electrical codes.
The power cord supplied with power supply may or may not include a power plug (see "Options" in Chapter l) at one end of
the cord. Terminating connections and a ground lug are attached to the other end of the cord.
See Figure 2-2 and proceed as follows:
1. If they are not already in place, position the strain relief connector ), safety cover , rubber boot , and
connector nut on the power cord .
2. Secure the ground wire to the chassis earth ground stud.
3. For single-phase operation, connect the neutral wire to the N input terminal and the line wire to the L input
terminal (this line is fused inside the supply).
4. For line-to-line operation from a three-phase source as shown in Figure 2-3, connect one phase to the N input
terminal and another phase to the L input terminal (this line is fused inside the supply).
Note The N terminal is not internally grounded.
5. Position the safety cover over the power input terminals and tighten the cover screws and strain relief connector
screws .
Figure 2-2. Connecting the Series 667xA Power Cord