Electrical Requirements
Refer to Table 9 and Table 10.
NOTE: Minimum wire sizes are obtained from Canadian Electrical Code Table 2 for 75°C Conductors and are intended for use as a guideline only. Electrical connections should be made only by a qualified electrical contractor in accordance with all applicable local and national requirements.
For 25, 30 and 35 Pound Gas and Steam Models:NOTE: Electrical specifications below are subject to change without notice. Always refer to product serial plate for most current specifications of product being installed.
NOTE: Use copper conductors only.NOTE: Connect to individual branch circuit.NOTE: 3 Phase Only – Each tumbler must be connected to its own individual branch circuit breaker, not fuses, to avoid the possibility of “single phasing” and causing premature failure of the motor(s).
| Terminal Block |
| Recommended |
| Recommended | |
Serial Plate | Current | Fuse or | Breaker | Minimum | ||
Connections | ||||||
Voltage | (Amps) | Breaker Rating | Poles | Conductor Size | ||
Required | ||||||
|
| (Amps) |
| [AWG (mm2)] | ||
120V/60Hz/1ph | L1, Neutral, | 12.0 | 15 | 1 | 14 (2.08) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
L1, L2, Neutral, | 6.7 | 10 | 2 | 14 (2.08) | ||
1ph | and ground |
|
|
|
| |
|
|
|
|
|
| |
120V/60Hz/1ph | L1, Neutral, | 7.5** | 10 | 1 | 14 (2.08) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
L1, L2, Neutral, | 4.5** | 10 | 2 | 14 (2.08) | ||
1ph | and ground |
|
|
|
| |
|
|
|
|
|
| |
100V/60Hz/1ph | L1, Neutral, | 11.0 | 15 | 1 | 14 (2.08) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
L1, Neutral, | 5.8 | 10 | 1 | 14 (2.08) | ||
1ph | and ground |
|
|
|
| |
100V/50Hz/1ph | L1, Neutral, | 12.1 | 20 | 1 | 12 (3.31) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
200V/50Hz/1ph | L1, Neutral, | 7.5 | 10 | 1 | 14 (2.08) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
L1, Neutral, | 7.5 | 10 | 1 | 14 (2.08) | ||
1ph | and ground |
|
|
|
| |
L1, L2, L3, | 3.2 | 10* | 3 | 14 (2.08) | ||
3ph | and ground |
|
|
|
| |
|
|
|
|
|
| |
240V/60Hz/3ph | L1, L2, L3, | 3.2 | 10* | 3 | 14 (2.08) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
200V/50Hz/3ph | L1, L2, L3, | 2.9 | 10* | 3 | 14 (2.08) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
L1, L2, L3, | 3.5 | 10* | 3 | 14 (2.08) | ||
3ph | and ground |
|
|
|
| |
|
|
|
|
|
| |
380V/50Hz/3ph | L1, L2, L3, | 1.5 | 10* | 3 | 14 (2.08) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
L1, L2, L3, | 1.6 | 10* | 3 | 14 (2.08) | ||
3ph | and ground |
|
|
|
| |
L1, L2, L3, | 1.6 | 10* | 3 | 14 (2.08) | ||
3ph | and ground |
|
|
|
| |
|
|
|
|
|
|
*3 Phase machines should not have fuses, breakers only.
**Special low Amp blower model, 25 Pound only
Table 9