Electrical Requirements

Electrical Requirements for Electric Models

Refer to Table 11, Table 12 and Table 13.

NOTE: Minimum wire sizes are obtained from Canadian Electrical Code Table 2 for 75°C Conductors and are intended for use as a guideline only. Electrical connections should be made only by a qualified electrical contractor in accordance with all applicable local and national requirements.

For 9 kW 25 Pound Electric Models:

NOTE: Electrical specifications below are subject to change without notice. Always refer to product serial plate for most current specifications of product being installed.

NOTE: Use copper conductors only.

NOTE: Connect to individual branch circuit.

NOTE: 3 Phase Only – Each tumbler must be connected to its own individual branch circuit breaker, not fuses, to avoid the possibility of “single phasing” and causing premature failure of the motor(s).

 

Terminal Block

 

Recommended

 

Recommended

Serial Plate

Current

Fuse or

Breaker

Minimum

Connections

Voltage

(Amps)

Breaker Rating

Poles

Conductor Size

Required

 

 

(Amps)

 

[AWG (mm2)]

400V/50Hz/3ph

L1, L2, L3,

16

20*

3

12 (3.31)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For 12 kW 25 Pound Electric Models:

 

Terminal Block

 

Recommended

 

Recommended

Serial Plate

Current

Fuse or

Breaker

Minimum

Connections

Voltage

(Amps)

Breaker Rating

Poles

Conductor Size

Required

 

 

(Amps)

 

[AWG (mm2)]

208V/60Hz/1ph

L1, L2, Neutral,

64

80

2

4 (21.2)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240V/60Hz/1ph

L1, L2, Neutral,

57

80

2

4 (21.2)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200V/50Hz/1ph

L1, Neutral,

63

80

1

4 (21.2)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230-240V/50Hz/

L1, Neutral,

58

80

1

4 (21.2)

1ph

and ground

 

 

 

 

 

 

 

 

 

 

200-208V/60Hz/

L1, L2, L3,

37

50*

3

6 (13.3)

3ph

and ground

 

 

 

 

 

 

 

 

 

 

200V/50Hz/3ph

L1, L2, L3,

36

50*

3

6 (13.3)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230-240V/50Hz/

L1, L2, L3,

33

50*

3

6 (13.3)

3ph

and ground

 

 

 

 

 

 

 

 

 

 

240V/60Hz/3ph

L1, L2, L3,

33

50*

3

6 (13.3)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380V/50Hz/3ph

L1, L2, L3,

20

25*

3

10 (5.26)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400-415V/50Hz/

L1, L2, L3,

18

25*

3

10 (5.26)

3ph

and ground

 

 

 

 

 

 

 

 

 

 

460-480V/60Hz/

L1, L2, L3,

16

25*

3

10 (5.26)

3ph

and ground

 

 

 

 

 

 

 

 

 

 

*3 Phase machines should not have fuses, breakers only.

Table 11

54

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

70269701