32 AIS® 3000 10-40kVA, 400V, Site Preparation and Installation Manual – 990-2258
System-Electrical Information
WARNING!
All electrical power and power control wiring must be installed by a qualified
electrician, and must comply with local and national regulations for maximum power
rating.
UPS ratings 10kVA
8 kW
15kVA
12 kW
20kVA
16 kW
30kVA
24 kW
40kVA
32kW
Input voltage (V)/per phase 3x400/
230V
3x400/
230V
3x400/
230V
3x400/
230V
3x400/
230V
Input current (nominal) (A) 12.4 18.6 24.8 37.2 49.6
Maximum input current (continuous, at
minimum mains voltage)/per phase
13.6 20.5 27.3 40.9 54.6
Input current protection for mains source
or single mains supply (external to UPS,
not supplied) (A)
3x20 3x35 3x50 3x63 3x80
Input current protection for bypass source
in dual mains configuration (external to
UPS, not supplied) (A)
20 35 50 63 80
Input frequency (Hz) range 40-70 40-70 40-70 40-70 40-70
Output voltage (on line). (V)
Minimum and maximum values (+/- 1%)
3x400/
230V
3x400/
230V
3x400/
230V
3x400/
230V
3x400/
230V
Output current (nominal) (A) 14.4 21.7 28.9 43.3 57.7
Maximum output current
(in bypass only at 110% overload per
phase)
15.9 23.8 31.8 47.6 63.5
Bypass input current (A)
(in bypass only at 110% overload, per
phase)
15.9 23.8 31.8 47.6 63.5
Neutral output current (with 100% switch
mode load) (A)
25.0 37.5 50.0 75.0 100.0
Output current protection (external to
UPS, not supplied) (A)
20 35 35 63 80
Output frequency range (Hz) 50/60 50/60 50/60 50/60 50/60
DC overcurrent protection and disconnect
switch for external safety: (A)
DC voltage rating of the battery supply
Maximum available battery short-circuit
current.
22
+/- 192
10 kA
33
+/- 192
10 kA
44
+/- 192
10 kA
66
+/- 192
10 kA
88
+/- 192
10 kA