This instruction sheet only provides introductory information on electrical specifications, functions, and wiring. The
program and instructions designed for DVP-EH2-L are compatible with those of DVP-EH2 series, and please refer to
"DVP-PLC Application Manual: Programming”. For how to purchase its peripheral devices, please refer to this
instruction sheet or “DVP-PLC Application Manual: Special Modules".
DVP-EH2-L is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device
(e.g. key or specific tools are required for opening the enclosure) in case danger and damage on the device may
occur.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all
the wiring again before switching on the power and DO NOT touch any terminal when the power is switched on.
Make sure the ground terminal is correctly grounded in order to prevent electromagnetic interference.
Introduction Product Profile & Outline
1 Battery socket cover
2 Function card/memory card cover
3 I/O terminals
4 I/O terminal No.
5 Extension module connection port cover
6 Input indicator
7 Output indicator
8 DIN rail clip
9 Communication port cover
10 DIN rail (35mm)
1
Mounting screw 5
Memory card port 9 COM1 (RS-232)
2
Direct mounting hole 6
POWER/RUN/BAT.LOW/ERROR indicator 10
COM2 (RS-485)
3
Battery socket 7
Extension module connection port 11
Run/Stop switch
4
Function card mounting hole 8
Left-side Extension module connection port
12
VR0/VR1
ENGLISH
Dimension
Unit: mm
Electrical Specification
Model
Item
32EH00
2-L
Power supply voltage 100 ~ 240VAC (-15% ~ 10%); 50/60Hz ± 5%
Fuse capacity 2A/250VAC
Power consumption 60VA
DC24V current supply 500mA
Power protection DC24V; output short-circuited
Withstand voltage 1,500V AC (Primary-Secondary); 1,500V AC (Primary-PE); 500V AC (Secondary-PE)
Insulation resistance > 5MΩ (all I/O point-to-ground: 500V DC)
Noise immunity
ESD: 8KV Air Discharge; EFT: Power Line: 2KV, Digital I/O: 1KV, Analog &
Communication I/O: 250V; Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV,
RS: 26MHz ~ 1GHz, 10V/m
Earth
The diameter of grounding wire shall not be less than that of L, N terminal of the power.
(When many PLCs are in use at the same time, please make sure every PLC is properly
grounded.)
Operation/storage Operation: 0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -25 ºC ~ 70 ºC (temperature); 5 ~ 95% (humidity)
Vibration/shock immunity International standards:IEC61131-2,IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC68-2-27
(TEST Ea)
Weight (g) R/T: 670/636
Input Point Specification
24VDC single common port input Specification
Items 10kHz 20kHz 60kHz Note
Input wiring type Change wiring from S/S to SINK or SOURCE
Input indicator LED display; light on = ON, light off = OFF
Input voltage (±10%) 24VDC
Input point configuration *3
*1
*2
Input impedance 4.7kΩ 3.3kΩ 4.7kΩ
Off On
> 4mA (16.5V)
> 6mA (18.5V)
> 4mA (16.5V)
Active Level
On Off
< 1.5mA (8V) < 2.2mA (8V) < 1.5mA (8V)
Off On
< 8us < 3.5us < 7.5us
Response time/
noise immunity
On Off
< 60us < 20us < 7.5us
*1: The bandwidth of input points
X10, X11, X14, and X15 is
20kHz.
*2: The bandwidth of input points
X0, X1, X4, and X5 is 60kHz.
*3: The bandwidth of the input
points other than the
high-speed input points listed
above is 10kHz.
*4: Input points X0 ~ X7and X10 ~
X17 can conduct 10 ~ 60ms
digital filter adjustment.
Output Point Specification
Single common port transistor output
Specification
Items Low speed High speed* Single common port relay output
Max. frequency 10kHz 200kHz Load ON/OFF control
Output indicator LED display; light on = ON, light off = OFF
Min. load -- 2mA/DC power supply
Working voltage 5 ~ 30V DC < 250V AC, 30V DC
Insulation Photo coupler isolation Magnetic isolation
Current specification 0.3A/1 point @ 40ºC
< 1kHz, 0.3A/1 point @ 40°C
≥ 1kHz, 30mA/1 point @ 40°C
2A/1 point (5A/COM)
75VA (conductive), 90W (resistive)
Off On
20us
Max. output
delay time
On Off
30us 0.2us 10ms
Over-current protection N/A
Mechanical life N/A 2×10
7
times (without load)
Electrical life N/A
1.5×10
5
times (5A 30V DC)
5×10
5
times (3A 120V AC)
3×10
4
times (5A 250V AC)
* Only Y0 and Y2 support high-speed output.
Installation & Wiring 3.1 How to Mount & Wiring Notes
How to install DIN rail:
DVP series PLC can be secured to a cabinet by using the DIN rail of 35mm in height and
7.5mm in depth. When mounting PLC to DIN rail, be sure to use the end bracket to stop any
side-to-side movement of PLC and reduce the chance of wires being loosen. A small retaining
clip is at the bottom of PLC. To secure PLC to DIN rail, place the clip onto the rail and gently
push it up. To remove it, pull the retaining clip down and gently remove PLC from DIN rail, as
shown in the figure.
How to screw: Please use M4 screw according to the dimension of the product.
DVP MPU
> 50mm
> 50mm
> 50mm
> 50mm
Please install PLC in an enclosure with sufficient space around it to allow heat
dissipation as shown in the figure.
Wiring:
To suit M3.5 screw terminals
Below 6.2
Below 6.2
1. Use O-type or Y-type terminal. See the figure in the left hand side for its
specification. PLC terminal screws should be tightened to 5 ~ 8 kg-cm (4.3 ~
6.9 in-Ibs) and please use only 60/75ºC copper conductor.
2. DO NOT wire empty terminal • . DO NOT place the input signal cable and
output power cable in the same wiring circuit.
3. DO NOT drop tiny metallic conductor into the PLC while screwing and wiring.
Tear off the sticker on the heat dissipation hole for preventing alien
substances from dropping in, to ensure normal heat dissipation of the PLC.
3.2 Wiring Notes
Power Input Wiring
The power input of DVP-EH2-L PLC is AC. When operating the PLC, please make sure that:
1. The input voltage should be current and its range should be 100 ~ 240V AC. The power should be
connected to L and N terminals. Wiring AC110V or AC220V to +24V terminal or input terminal will result in
serious damage on the PLC.
2. The AC power input for PLC MPU and I/O extension modules should be ON or OFF at the same time.
3. Use wires of 1.6mm (or longer) for the grounding. The power shutdown of less than 10ms will not affect the
operation of the PLC. However, power shutdown time that is too long or the drop of power voltage will stop
the operation of the PLC and all outputs will go OFF. When the power supply turns normal again, the PLC
will automatically return to its operation. Please be aware of the latched auxiliary relays and registers inside
the PLC when programming.
AC Power Input
100~240
VAC
0.5A is the maximum power supply for
+24V power supply output terminal. DO
NOT connect other external power
supplies to this terminal. Every input
terminal requires 6 ~ 7mA to be driven;
e.g. the 16-point input will require
approximately 100mA. Therefore, +24V
cannot give output to extermal load that is
more than 400A.
Safety Wiring
Since a PLC controls many devices, actions of any device may affect actions of other devices, and the
breakdown of any one device may cause the breakdown of the whole auto-control system and danger.
Therefore, we suggest you wire a protection circuit at the power input terminal, as shown in the figure below.
AC power supply load
Power circuit protection fuse (3A
Power indicator
Emergency stop
This button can cut off the system power supply when accidental
emergency takes place.
System circuit isolation device
The device is made of electromagnetic contactor and relay as the
switch to prevent the instability of system when the power is
intermittently supplied.
DVP-PLC (main processing unit)
Earth
MC
MC
NL
1
1
2
3
4
5
6
8
Guard
Limit
MC
Power supply AC: 100 ~ 240VAC
Input Point Wiring
There are two types of DC inputs, SINK and SOURCE.
Input point loop equivalent circuit Wiring loop
DC Signal IN
S/S
X0
Sinking
SINK mode
(common port for current input S/S)
24VDC
24G
X0
S/S
+24V SINK
+5V
24G S/S X0 X1 X2+24V
Sink Type
Input point loop equivalent circuit Wiring loop
DC Signal IN
S/S
X0
Sourcing
SOURCE mode
(common port for current output S/S)
24VDC
24G
X0
S/S
+24V SOURCE
+5V
24G S/S X0 X1 X2+24V
Source Type
Output Point Wiring
Relay (R) contact circuit wiring
Y0
RY
LED
C0
LOAD
POWER
DVP-**-**-**-R
RELAY OUTPUT
2
3
1
5
C0Y0 Y1 C1 Y3 Y4 C2 Y6
Y7
4
MC1
MC2
7
10
3
2
8
9
6
Flywheel diode: To extend the life span of contact
Emergency stop: Uses external switch
Fuse: Uses 5 ~ 10A fuse at the common port of output contacts to protect the output circuit
Varistor: To reduce the interference on AC load
Empty terminal: not in use
DC power supply
Neon indicator
A C power supply
Incandescent light (resistive load)
Manually exclusive output: Uses external circuit and forms an interlock, together with the PLC
internal program, to ensure safety protection in case of any unexpected errors.
Transistor (T) contact circuit wiring
Y0
LED
C0
TRANSISTOR OUT PUT
LOAD
1. NPN
< 0.3A
MC1
MC2
2
3
1
C0Y0 Y1 C1 Y4 Y5 Y6 Y7
5
4
5
3
4
Y0
LED
ZP0
TRANSISTOR OU TPUT
LOAD
2. PNP
< 0.3A
Up0
MC1
MC2
2
3
1
Up0
Zp0
Up1
Zp1
Y1 Y10
Y0
Y11
3
5
5
4
DC power supply
Emergency stop
Circuit protection fuse
Flywheel diode + inductive load
Manually exclusive output: Uses external circuit and forms an interlock, together with the PLC
internal program, to ensure safety protection in case of any unexpected errors.
DVP-EH2
DVP-PLC
DVP-PLC
(OPEN TYPE)
1
2
3
4
5
6
7
8 DIN
9
10 DIN (35mm)
1 5 9 COM1 (RS-232)
2
6
10
COM2 (RS-485)
3
7
11
Run/Stop
4
8
12
VR0/VR1
mm
DVP32EH002-L
100 ~ 240V AC (-15% ~ 10%); 50/60Hz ± 5%
2A/250V AC
60VA
DC24V 500mA
DC24V
1,500V AC (Primary-Secondary); 1,500V AC (Primary-PE); 500V AC (Secondary-PE)
5 M 500V DC
ESD: 8KV Air Discharge; EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O:
250V; Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m
L, N PLC
0°C ~55°C 50 ~ 95% 2
-25°C ~70°C 5 ~ 95%
/ IEC 6 1131-2, IEC 68-2-6 (TEST Fc) / IEC 61131-2 & IEC 68-2-27 (TEST Ea)
, (g) R/T: 670/636
24VDC
10kHz 20kHz 60kHz
S/S SINK SOURCE
LED ON OFF
(±10%) 24V DC
* 3 * 1 * 2
4.7kΩ 3.3kΩ 4.7kΩ
OffOn > 4mA (16.5V)
> 6mA (18.5V)
> 4mA (16.5V)
OnOff < 1.5mA (8V) < 2.2mA (8V) < 1.5mA (8V)
OffOn < 8 us < 3.5 us < 7.5 us
OnOff < 60 us < 20 us < 7.5 us
* 1 X10, X11, X14, X15
20kHz
* 2 X0, X1, X4, X5
60kHz
* 3
10kHz
* 4 X0~X17 10 ~ 60
ms