Chapter 6 Fault Code Information and Maintenance
Terminals and wiring of main circuit
|
|
| Maintenance | |||
| Check Items | Methods and Criterion |
| Period |
| |
|
|
|
| |||
Daily | Half | One | ||||
|
|
| ||||
|
|
| Year | Year | ||
|
|
|
|
|
| |
| If the wiring shows change of |
|
|
|
| |
| color change or deformation due | Visual inspection |
| { |
| |
| to overheat |
|
|
|
| |
|
|
|
|
|
| |
| If the insulation of wiring is |
|
|
|
| |
| damaged or the color has | Visual inspection |
| { |
| |
| changed |
|
|
|
| |
|
|
|
|
|
| |
| If there is any damage | Visual inspection |
| { |
| |
|
|
|
|
|
| |
DC capacity of main circuit |
|
|
|
| ||
|
|
| Maintenance | |||
| Check Items | Methods and Criterion |
| Period |
| |
|
|
|
| |||
| Daily | Half | One | |||
|
|
| ||||
|
|
| Year | Year | ||
|
|
|
|
|
| |
| If there is any leakage of liquid, |
|
|
|
| |
| change of color, cracks or | Visual inspection | { |
|
| |
| deformation |
|
|
|
| |
|
|
|
|
|
| |
| Measure static capacity when | Static capacity ≥ initial value X 0.85 |
| { |
| |
| required |
|
| |||
|
|
|
|
| ||
|
|
|
|
|
| |
Resistor of main circuit |
|
|
|
| ||
|
|
| Maintenance | |||
| Check Items | Methods and Criterion |
| Period |
| |
| Daily | Half | One | |||
|
|
| ||||
|
|
| Year | Year | ||
|
|
|
|
|
| |
| If there is any peculiar smell or | Visual inspection, smell |
|
|
| |
| insulator cracks due to |
| { |
| ||
| overheating |
|
|
|
| |
|
|
|
|
|
| |
|
| Visual inspection or measure with |
|
|
| |
| If there is any disconnection | multimeter after removing wiring |
| { |
| |
| between +2(+2/B1) ~ - |
|
| |||
|
| Resistor value should be within ± 10% |
|
|
|
Revision July 2008, EG03, SW V1.06 |