19 electrolux refrigerant pipe connection

19 electrolux refrigerant pipe connection

4. Flaring work

electrical work electrolux 20

Electrical work

Electric safety regulations for the initial Installation

A)Firmly hold copper pipe in a die in the dimension shown in the table below.

Bar

Copper pipe

1. If there is serious safety problem

about the power supply, the

technicians should refuse to install

the air conditioner and explain to

5. According to the attached Electrical

Connection Diagram located on the

panel of the outdoor unit to connect

the wire.

OUTER

DIAMETER (mm)

6,35

9,53

12,70

16

A (mm)

Máx.

Mín.

1,3

0,7

1,6

1,0

1,8

1,0

2,4

2,2

Handle

Yoke

Red arrow mark

Clamp handle

 

the client until the problem is

 

solved.

2.

Power voltage should be in the

 

range of 90%~110%of rated

 

voltage.

3.

The creepage protector and main

 

power switch with a 1.5 times

 

capacity of Max. Current of the unit

 

should be installed in power circuit.

4.

Ensure the air conditioner is

 

grounded well.

6. All wiring must comply with local

and national electrical codes and be

installed by qualified and skilled

electricians.

7. An individual branch circuit and

single receptacle used only for this

air conditioner must be available.

See the following table for

suggested wire sizes and fuse

specifications:

Connection Adjustment

1.Align the pipes to be connected.

2.Unscrew the flare nut with your fingers and then with a wrench and screw wrench, as shown in the following figure.

Caution: Excessive torque can break nut depending on installation conditions.

MODEL

POWER SUPPLY

INPUT RATED AMP

CABLE

Switch / Fuse

SIZE

 

 

9000 Btu’s

220-240V~/ 50Hz

10A

1 mm²

220-230V~/ 60Hz

 

 

 

 

 

12000 Btu’s

220-240V~/ 50Hz

16A

1,5 mm²

18000 Btu’s

220-230V~/ 60Hz

 

 

 

220-240V~/ 50Hz

25A

2,5 mm²

Indoor unit

Flare

tubing

nut

OUTER

DIAMETER (mm)

Pipings

TIGHTENING

TORQUE(cm)

ADDITIONAL TIGHTENING

TORQUE(cm)

24000 Btu’s

32A

> 2,5 mm²

220-230V~/ 60Hz

Note: The supply voltage must be consistent with the rate voltage of the air conditioner.

6,35

1570 (160 kgf/cm)

1960 (200 kgf/cm)

9,53

2940 (300 kgf/cm)

3430 (350 kgf/cm)

12,70

4900 (500 kgf/cm)

5390 (550 kgf/cm)

16

7360 (750 kgf/cm)

7850 (800 kgf/cm)