Electrolux EAS(C,E)12P5ASK(W,S,M), EAS(C,E)24P5ASK(W,S,M) Air purging, electrolux electrical work

Models: EAS(C,E)12P5ASK(W,S,M) EAS(C,E)09P5ASK(W,S,M) EAS(C,E)18C2ASK(W,S,M) EAS(C,E)12C2ASK(W,S,M) EAS(C,E)24C2ASK(W,S,M) EAS(C,E)18P5ASK(W,S,M) EAS(C,E)24P5ASK(W,S,M) EAS(C,E)09C2ASK(W,S,M)

1 28
Download 28 pages 50.6 Kb
Page 14
Image 14
25 electrolux electrical work

25 electrolux electrical work

Caution

After the confirmation of the above conditions, prepare the wiring as follows:

1.

Never fail to have an individual power circuit specifically for the air

 

conditioner. As for the method of wiring, be guided by the circuit diagram

 

posted on the inside of control cover.

2.

The screw which fasten the wiring in the casing of electrical fittings are

 

liable to come loose from vibrations to which the unit is subjected during

 

the course of transportation. Check them and make sure that they are all

 

tightly fastened. (If they are loose, it could cause burn-out of the wires.)

3.

Specification of power source.

4.

Confirm that electrical capacity is sufficient.

electrical work electrolux 26

Air purging with vacuum pump

1.Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.

2.When relocate the unit to another place, perform evacuation using vacuum pump.

3.Pipe length and refrigerant amount:

5.

See to that the starting voltage is maintained at more than 90 percent of the

 

rated voltage marked on the name plate.

6.

Confirm that the cable thickness is as specified in the power source

 

specification.

7.

Always install an earth leakage circuit breaker in a wet or moist area.

8.

The following would be caused by voltage drop. Vibration of a magnetic

 

switch, which will damage the contact point, fuse breaking, disturbance of

 

the normal function of the overload.

9.

The means for disconnection from a power supply shall be incorporated in

Connective

pipe length

Less than 5 m

5~10 m

Air purging

metod

Use vacuum pump.

Use vacuum pump.

Additional amount of

refrigerant to be charged

Liquid side: Ö6.35

(Pipe lenght) x 30g

the fixed wiring and have an air gap contact separation of at least 3mm in

each active (phase) conductors.

Air purging

Caution in handling the packed valve

1.Open the valve stem until it hits against the stopper. Do not try to open it further.

2.Securely tighten the valve stem cap with a spanner or the like. Valve stem cap tightening torque (See Tightening torque table in page 19).

Air and moisture in the refrigerant system have undesirable effects as indicated below:

Refrigerant

Flare nut

1. Pressure in the system rises.

parts in the refrigeration system.

Outdoor unit

Indoor unit

2.

Operating current rises.

3.

Cooling or heating efficiency

 

drops.

4.

Moisture in the refrigerant circuit

 

may freeze and block capillary

6. Therefore, the indoor unit and

tubing between the indoor and

outdoor unit must be leak tested

and evacuated to remove any

noncondensables and moisture

AGas

B

C

D

Stopper

Cap

tubing.

from the system.

Packed valve

Half union

Valve body

 

Valve stem

5. Water may lead to corrosion of

Page 14
Image 14
Electrolux EAS(C,E)12P5ASK(W,S,M) electrolux electrical work, Air purging with vacuum pump, electrical work electrolux