FS-8700-70 WS3000 Tabs Manual Page 5 of 14

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

3. Hardware Connections

The FieldServer is connected to the WS3000 as shown below.

Configure the WS3000 according to manufacturer’s instructions.

WS3000
BASE NAME:
FILE NAME:
FIELDSERVER
WESTRONIC WS3000
CONNECTION DIAGRAM
DATE: 4/2/04
BY: MC
(408)-262-2299
FieldServer
RJ45 Socket
Use one of RS-232 ports P1-P8
148pins
DB
RS-232
GHK L
RS-422
485LDRC
B&B Electronics RS-
232 to RS-422
Converter
A
CGND
F+10 to 30V DC
GND
+
Power Supply
Dip Switch Settings
Sw Setting Meaning
1-4 Down (off) RS-422
5Up (on) Terminated
6-7 Down (off) Unused baud rates
8Up (on) 2400 baud
Rx-Rx+Tx-Tx+
5, 6, 7, 8,pins
Use one of Channels 3-9
Chan Connector no
3, P11
4, P3
5, P10
6, P8
8, P9
7, P1
9, P2
Jumper Pins
Z2, 2-7
Z2, 3-6
Z2, 4-5
Z1, 4-5
Z1, 2-7
Z1, 3-6
Z1, 1-8
Chan
3
4
5
6
7
8
9
RS-422 Rx termination strapping
Install a jumper on the
indicated pins
according to the
channel used
Refer to Datasheet for setting other baud rates