INSTALLATION
Continued
CAUTION:Useonlynew,black
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up.
NPT tap must be upstream from heater (see
Figure 13).
IMPORTANT: Install equipment valve in an
accessible location. The equipment shutoff
valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special
requirements for locating equipment shutoff
valve to fireplaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
We recommend that you install a sediment trap in supply line as shown in Figure 14. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contami- nants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fittings.
PROPANE/LP |
| |
From External Regulator |
| |
(11" W.C.** to 14" W.C. |
| |
Pressure) | Equipment Shutoff | |
NATURAL | ||
From Gas Meter | Valve With 1/8" NPT | |
(5" W.C.** to | Tap* | |
10.5" W.C. |
| |
Pressure) | Gas | |
|
| Regulator |
| 3" Minimum | |
Tee | Pipe Cap | Approved Flexible |
Gas Hose (if allowed | ||
Joint | Nipple | by local codes) |
Sediment Trap
Figure 13 - Gas Connection
*Purchase the optional equipment shutoff valve from your dealer.
**Minimum inlet pressure for purpose of input adjustment.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.
WARNING:Neveruseanopen flame to check for a leak. Apply a noncorrosive leak detection fluid toalljoints.Bubblesformingshow a leak. Correct all leaks at once.
CAUTION: Make sure external regulator has been installed between propane/LP supply and heater.SeeguidelinesunderConnecting to Gas Supply, page 13.