Fireplace Installation

Continued

8"

MIN.

 

(20.

 

3cm)

 

 

36

1

 

 

 

 

 

 

 

 

/

 

 

 

 

 

 

 

2"

 

 

 

.

52

/ (92. MIN.

 

 

 

1

 

 

7cm)

 

 

 

 

 

2"

 

 

 

MIN

 

 

.MIN.

16"

 

 

(133

3cm)

 

 

 

 

 

 

 

.

 

 

 

 

 

 

(40

 

6cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

NONCOMBUSTIBLE

 

 

 

 

 

 

 

 

HEARTH EXTENSION

 

 

 

Figure 9 - Hearth Extensions

 

 

 

 

 

 

 

 

Noncombustible

 

 

 

 

 

Hearth

 

 

 

 

 

 

 

 

Extension

 

 

 

 

 

 

 

 

8" Max.

 

 

1 1/2" Typ.

“Z” Type Ember

Protector

 

 

 

 

 

 

 

 

Noncombustible

 

 

 

 

 

 

 

 

Hearth Extension

 

 

 

 

 

 

 

 

K” Factor

 

 

 

 

 

 

.84

 

 

 

1 1/2" Typ.

 

 

 

 

 

 

 

 

 

Ember Protector

Figure 10 - Raised Hearth Extension

Mantel Clearances

Woodwork such as wood trims, mantels or any other combustible material projecting from

the front face must not be placed within 9" of fireplace opening.

Combustible materials above and projecting more than 1 1/2" from the fireplace front face (see Figure 11) must not be placed less than 12" from effective opening of the fireplace (NFPA STD 211, Sec. 7-3.3.3).

Mantels or any other combustible material may also come up to the side edge of the black metal face of the fireplace only if the projection from the front face falls within limits shown in Figure 12.

 

2" X 4" Stud

Drywall

 

Combustible

 

Materials

 

33°

 

6" Nom.

 

(15.2 cm)

 

12" Min.

 

(30.4 cm)

 

9" Min.

 

(22.8 cm)

Fireplace Side View

Front

3" Nom.

Face

(7.6 cm)

Fireplace Front View

1 1/2" Max.

(3.8 cm)

 

Figure 11 - Mantel Clearances to

Combustible Materials

Top View of Fireplace

 

Seal Gaps with

 

Noncombustible

Drywall

 

 

Mortar or Adhesive

4"

 

 

2 3/4" Max.

 

 

(6.98 cm)

(Approx.)

 

 

 

 

 

(10.1 cm) 33°

 

 

 

Nom.

 

 

 

 

4 3/8"

 

Combustible

 

Min.

 

Material Must

6" Nom.

(11.1 cm)

Not Overlap

 

 

Black Metal

(15.2 cm)

 

 

Front Face

Figure 12 - Mantel Clearances to Metal

Face

Venting Installation

Optional Outside air Kit

The installation of an outside air kit should be performed during the rough framing of the fireplace due to the nature of it’s location. Outside combustion air is accessed through and exterior wall or a vented crawl space.

Maximum height for air inlet above the fireplace platform must be no less than 3 feet below chimney cap.

For further details on installation of outside air kit, please refer to instructions included with air kit.

CAUTION:Airinletductsmust

not terminate in attic space.

6

www.fmiproducts.com

115603-01D