Venting Installation
Continued
Storm | Overlap | |
Collar | ||
Shingles Top | ||
Flashing | ||
and Sides Only | ||
Cone | ||
|
Nail Only
Outer
Perimeter
of Flashing
Underlap
Shingles
at Bottom
Figure 13 - Flashing Installation
Installing Flashing on a Metal Roof
When installing the flashing on a metal roof, it is required that putty tape be used between the flashing and the roof. The flashing must be secured to the roof using #8 x 3/4" screws and then sealed with roof coating to prevent leakage through the screw holes. A roof coating must also be applied around the perimeter of the flashing to provide a proper seal.
Storm Collar Installation
Place storm collar over pipe and slide down until it is snug against the open edge of the flashing (see Figure 14). Apply waterproof caulk around the perimeter of the collar to provide a proper seal.
Chimney | Waterproof |
Pipe | Caulk |
Storm | Flashing |
Collar |
CAUTION: Do not seal openings on the rooftop flashing. Follow the installation instructions provided with the termination being used.
Stainless | ||
Level of | ||
Inner Flue | ||
Flue Gas | ||
Pipe | ||
Outlet | ||
|
Secure |
| |
Termination | Waterproof | |
to Outer | ||
Caulking | ||
Pipe with 3 | ||
Screws | Storm | |
| Collar | |
| Flashing | |
Overlap | Underlap | |
Shingles (Top and Sides | ||
Shingles | ||
of Flashing Base) | ||
| ||
Figure 15 - Termination |
Chase installations
Instructions for chase installations are included with the chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another. Terminations be separated a minimum of 24" center to center and stacked at a minimum vertical height difference of 18" (see Figure 16).
Note: If a decorative shroud is to be installed, contact the manufacturer for specifications.
Figure 14 - Storm Collar
Terminations/Spark Arrestor
The fireplace system must be terminated with the listed round top or chase terminations. In any case, refer to the installation instructions supplied with the termination.
18" Min.
Typ.
24" Min.
24" Min.
Figure 16 - Multiple Chase Installation
10 | www.fmiproducts.com |