Troubleshooting

Mainly detect:

Whether the unit voltage is too high? Whether the work voltage is too low?

Out of step occurs once the unit is powered on.

Is stop time of the compressor longer than 3 minutes?

Are the wires for the compressor connected correctly? Is connection sequence right?

Is the connection made in clockwise direction?

Connect the wires correctly

Replace the control panel AP1

If the fault is eliminated?

Replace the compressor

Out of step occurs in operation

Is the outdoor fan working normally?

Is the outdoor unit blocked by foreign objects?

Replace the

control panel AP1

If the fault is eliminated?

Replace the compressor

Check if the fan terminal

 

Replace the fan

O FAN is connected correctly

 

 

capacitor C1

 

 

Replace the outdoor fan

Remove foreign objects

End

End

58

Page 58
Image 58
Friedrich MR09C1H, MW12C1H, MW09C1H, MR12C1H manual Is stop time of the compressor longer than 3 minutes?