2 - 98
35 SIEMENS PLC • 4
Wiring
The following is a diagram to show the wiring of the cable which connects POD to PLC.
RS-422
Wiring Diagram 1
Setting of Terminal Resistance
Set the dip switch 7,8 of POD to OFF.
Connect terminal registance to the POD serial connector (CN1) as follows.
If terminal registance is not connected, the communication error may occur.
PLC
D-sub  25pin(Male:     )
FG
SG
+SD
-SD
+RD
-RD
7
1
12
13
24
25
SG
TXD/RXD
TXD/RXD
5
3
8
D-sub  9pin(Male:     )
* Use twist shielded cables.
POD  (CN1)
D-sub  25pin(Male:     )
FG
SG
5V
+SD
-
SD
+RD
-
RD
7
1
9
12
13
24
25
POD  (CN1)
220Ω
390Ω
390Ω