Placement of Standby Generator to REDUCE THE RISK OF FIRE
The National Fire Protection Association (NFPA) standard |
|
| ||
| WARNING Exhaust heat/gases could ignite combustibles | |||
NFPA 37 establishes criteria for minimizing the hazard |
| or structures resulting in death or serious injury. | ||
of fire during the installation and operation of stationary |
|
| ||
combustion engines. NFPA 37 limits the spacing of an |
|
| ||
enclosed generator from openings in walls, structures and | • | Exhaust outlet side of weatherproof enclosure must have at least | ||
combustible materials outside the enclosure. |
| |||
|
| 5 ft. (1.5 m) minimum clearance from any structure, shrubs, trees | ||
The placement requirements provided are based on |
| or any kind of vegetation. | ||
compliance to NFPA 37 2010 section 4.1.4 and a | • | Standby generator weatherproof enclosure must be at least | ||
demonstration fire test. Details of compliance testing can be |
| 5 ft. (1.5 m) from windows, doors, any wall opening, shrubs or | ||
| vegetation over 12 inches (30.5 cm) in height. | |||
found in section National Fire Protection Association (NFPA) |
| |||
• | Standby generator weatherproof enclosure must have a minimum | |||
standard NFPA 37 requirements and testing. |
| |||
|
| of 5 ft. (1.5 m) overhead clearance from any structure, overhang | ||
|
|
| ||
|
|
| or trees. | |
|
| • | DO NOT place weatherproof enclosure under a deck or other type | |
|
|
| of structure that may confine airflow. | |
|
| • | Use only flexible steel fuel line provided. Connect provided fuel line | |
|
|
| to generator. DO NOT use with or substitute any other flexible fuel | |
|
|
| line. | |
B |
| • | Smoke detector(s) MUST be installed and maintained indoors | |
REPRODUCTION | ||||
|
|
| according to the manufacturer’s instructions/recommendations. | |
|
|
| Carbon monoxide alarms cannot detect smoke. | |
|
| • | DO NOT place weatherproof enclosure in manner other than | |
|
|
| shown in illustrations. |
|
| NOT |
|
Examples of standby generator locations to reduce the |
| ||
risk of fire: |
|
| |
Legend for Generator Locations to reduce the isk of fire. | Vertical learances | ||
A | Standby weatherproof enclosureformust be at least 5 ft |
|
(1.5 m) from windows, doors, any wall opening, shrubs |
| |
or vegetation over 12 inches (30.5 cm) in height. | Structure | |
Exhaust outlet side of weatherproof enclosure must | ||
C | ||
have at least 5 ft (1.5 m) minimum clearance from any | ||
| ||
structure, shrubs, trees or any kind of vegetation. |
|
C | Standby weatherproof enclosure must have a |
|
| minimum of 5 feet (1.5 m) overhead clearance from | 5 ft (1.5 m) |
any structure, overhang or trees.
NOTICE DO NOT place weatherproof enclosure under a deck or other type of covered structure that may confine airflow.
B |
|
|
|
|
|
|
|
|
| 5 ft (1.5 m) |
|
|
| ||
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Standby | |
|
|
|
|
| |||
| Exhaust | ||||||
| Direction |
|
| ||||
|
|
|
|
|
|
|
|
|
| Center of Exhaust Panel |
14