Auxiliary Control Switches
These switches are located behind the room cabinet under the control panel.
2900 and 3900 Series
Switches | Description |
|
Left Switches |
|
|
(1) | ALL I2R | Heat pump override — |
|
| Down — Normal heat pump operation |
|
| Up — resistance heat only (3900 Series only) |
(2) | C: FAN | Fan control for cooling operation — |
|
| Down — Fan Continuous |
|
| Up — Fan Cycle |
(3) | H: FAN | Fan control for heating operation — |
|
| Down — Fan Cycle |
|
| Up — Fan Continuous |
(4) | CLASS 2 | Remote Thermostat Mode — |
|
| Down — Unit Control |
|
| Up — Remote Thermostat |
(5) | LOAD SHED | Load Shedding when connected to Central Desk Control System — |
|
| Down — Fan shuts off with unit |
|
| Up — Fan under “Smart Fan” settings |
(6) | FREEZ S | Freeze Sentinel™ Override — |
|
| Down — Freeze Sentinel ON |
|
| Up — Freeze Sentinel OFF |
(7) | CONST FAN | Constant Fan — |
|
| Down — Fan runs normally |
|
| Up — Fan runs when unit is in STOP position |
Right Switches |
| |
TL1 – TL3 |
| Cooling temperature limiting (See table at bottom of page) |
TL4 – TL6 |
| Heating temperature limiting (See table at bottom of page) |
(7) |
| Heat Sentinel switch — |
|
| Down — Heat Sentinel OFF |
|
| Up — Heat Sentinel ON |
(8) |
| Heat Boost (3900 series only) — |
|
| Down — Heat Boost OFF |
|
| Up — Heat Boost ON |
Auxiliary (2900 and 3900 series)
3900 Series shown | UP |
|
|
|
|
|
|
|
|
| DOWN | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
|
|
ALLI2R (All Electric Heat) (3900 Series models only)
C:FAN CN
H:FAN CY
LOAD SHEDDING (CDC) FREEZ Sen (Freeze Sentinel)
CONST FAN (Constant ON Fan)
NO FUNCTION (Reserved for future use)
1 | 2 | 3 |
HIGH C4OOL5 6
7 | 8 |
UP
DOWN
HEAT BOOST
(3900 Series models only) Heat Sentinel
TL1 (H) (Temp. Limit
TL1 (C) (Temp. Limit
Cooling and Heating temperature limits are set independently, temperature limiting switches are in
Cooling Temperature Limits
Switches Up |
| NONE | 1 | 1, 2 | 2 | 2, 3 | 1, 2, 3 | 1, 3 | 3 |
|
|
|
|
|
|
|
|
|
|
|
| 60 | 64 | 66 | 68 | 70 | 72 | 74 | 76 |
|
|
|
|
|
|
|
|
|
|
| Heating Temperature Limits |
|
|
|
| ||||
Switches Up |
| 6 | 4, 6 | 4, 5, 6 | 5, 6 | 5 | 4, 5 | 4 | NONE |
|
|
|
|
|
|
|
|
|
|
|
| 65 | 70 | 72 | 74 | 76 | 78 | 80 | 85 |
|
|
|
|
|
|
|
|
|
|
12