3 of 5

Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514,
ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power
decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60°F). Sound output ratings from certain points on the generator
subject to change based on installation parameters.

Generator

Model 005882-1, 005870-1 (8 kW)
005883-1, 005871-1,
0060651-1 (10 kW)
005884-1, 005872-1,
006052-1 (14 kW)
Rated Maximum Continuous Power Capacity (LP) 8,000 Watts* 10,000 Watts* 14,000 Watts*
Rated Maximum Continuous Power Capacity (NG) 7,000 Watts* 9,000 Watts* 13,000 Watts*
Rated Voltage 240 240 240
Rated Maximum Continuous Load Current – 240 Volts 33.3 LP/29.2 NG 41.6 LP/37.5 NG 58.3 LP/54.2 NG
Total Harmonic Distortion Less than 5% Less than 5% Less than 5%
Main Line Circuit Breaker 35 Amp 45 Amp 60 Amp
Phase 1 1 1
Number of Rotor Poles 2 2 2
Rated AC Frequency 60Hz 60Hz 60Hz
Power Factor 111
Battery Requirement (not included) Group 26R 12 Volts and 525
Cold-cranking Amperes Minimum
Group 26R 12 Volts and 525
Cold-cranking Amperes Minimum
Group 26R 12 Volts and 525
Cold-cranking Amperes Minimum
Unit Weight (Pounds/Kilos) 340/154.2 387/175.4 439/199.1
Dimensions (L x W x H) Inches/mm 48 x 25 x 29 (1218 x 638 x 732)
Sound output in dB(A) at 23 ft. with generator operating at normal load 62 63 66

Engine

Type of Engine GENERAC OHVI GENERAC OHVI V-TWIN GENERAC OHVI V-TWIN
Number of Cylinders 122
Displacement 410cc 530cc 992cc
Cylinder Block Aluminum w/Cast Iron Sleeve Aluminum w/Cast Iron Sleeve Aluminum w/Cast Iron Sleeve
Valve Arrangement Overhead Valve Overhead Valve Overhead Valve
Ignition System Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto
Governor System Electronic Electronic Electronic
Compression Ratio 9.5:1 9.5:1 9.5:1
Starter 12 Vdc 12 Vdc 12 Vdc
Oil Capacity Including Filter Approx. 1.5 Qts./1.4L Approx. 1.7 Qts./1.6L Approx. 1.9 Qts./1.8L
Operating RPM 3,600 3,600 3,600
Fuel Consumption
Natural Gas ft3/hr.
1/2 Load
Full Load
Liquid Propane ft3/hr (gal/hr) [Liter/hr]
1/2 Load
Full Load
77
139
34 (0.94) [3.56]
62 (1.68) [6.36]
102
156
46 (1.25) [4.73]
70 (1.93) [7.31]
156
220
58 (1.56) [5.91]
84 (2.30) [8.71]
Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas
For Btu content, multiply ft3/hr x 2520 (LP) or ft3/hr x 1000 (NG)

Controls

2-Line Plain Text LCD Display Simple user interface for ease of operation.
Mode Switch
-Auto Automatic Start on Utility failure. 7 day exerciser.
-Off Stops unit. Power is removed. Control and charger still operate.
-Manual/Test (start) Star t with starter control, unit stays on. If utility fails, transfer to load takes place.
Programmable start delay between 10-30 seconds Standard
Engine Start Sequence Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration).
Engine Warm-up 5 seconds
Engine Cool-Down 1 minute
Starter Lock-out Starter cannot re-engage until 5 sec. after engine has stopped.
Smart Battery Charger Standard
Automatic Voltage Regulation with Over and Under Voltage Protection Standard
Automatic Low Oil Pressure Shutdown Standard
Overspeed Shutdown Standard, 72Hz
High Temperature Shutdown Standard
Overcrank Protection Standard
Safety Fused Standard
Failure to Transfer Protection Standard
Low Battery Protection Standard
50 Event Run Log Standard
Future Set Capable Exerciser Standard
Incorrect Wiring Protection Standard
Internal Fault Protection Standard
Common External Fault Capability Standard
8/10/14kW specifications
8/10/14kW
®