QT060
OPERATING DATA
  | 
  | 
  | QT060  | 
  | 
kW RATING  | 
  | 
  | 60  | 
  | 
  | 
  | 
  | 
  | 
  | 
ENGINE SIZE  | 
  | 
  | 2.4 Liter Inline 4  | 
  | 
  | 
  | 
  | 
  | 
  | 
GENERATOR OUTPUT VOLTAGE/KW - 60Hz  | 
  | KW  | AMP | CB Size | 
120/208V,   | 
  | 60  | 208  | 250  | 
120/240V,   | 
  | 60  | 180  | 200  | 
277/480V,   | 
  | 60  | 90  | 100  | 
  | 
  | 
  | 
  | 
  | 
GENERATOR LOCKED ROTOR KVA | 
  | 
  | 
  | 
  | 
AVAILABLE @ VOLTAGE DIP OF 35% | 
  | 
  | 
  | 
  | 
Single phase or 208/240   | 
  | 
  | 120  | 
  | 
480V   | 
  | 
  | 141  | 
  | 
  | 
  | 
  | ||
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) | Natural Gas  | Propane  | ||
  | 
  | (ft3/hr.)  | (gal/hr.)  | cu ft/hr  | 
Exercise cycle  | 
  | 123  | 1.34  | 49.3  | 
25% of rated load  | 
  | 267  | 2.7  | 101  | 
50% of rated load  | 
  | 483  | 5.0  | 183  | 
75% of rated load  | 
  | 672  | 7.0  | 255  | 
100% of rated load  | 
  | 862  | 9.0  | 327  | 
  | 
  | 
  | 
  | 
  | 
ENGINE COOLING | 
  | 
  | 
  | 
  | 
Air flow (inlet air including alternator and combustion air)  | ft3/min.  | 
  | 3,280  | 
  | 
System coolant capacity  | US gal.  | 
  | 2.5  | 
  | 
Heat rejection to coolant  | BTU/hr.  | 
  | 270,000  | 
  | 
Max. operating air temp. on radiator  | °C (°F)  | 
  | 60 (150)  | 
  | 
Max. ambient temperature  | °C (°F)  | 
  | 50 (140)  | 
  | 
  | 
  | 
  | 
  | 
  | 
COMBUSTION AIR REQUIREMENTS  | 
  | 
  | 
  | 
  | 
Flow at rated power 60 Hz  | cfm  | 
  | 180  | 
  | 
  | 
  | 
  | 
  | 
  | 
SOUND EMISSIONS IN DBA  | 
  | 
  | 
  | 
  | 
Exercising at 7 meters  | 
  | 
  | 65  | 
  | 
Normal operation at 7 meters  | 
  | 
  | 72  | 
  | 
  | 
  | 
  | 
  | 
  | 
EXHAUST  | 
  | 
  | 
  | 
  | 
Exhaust flow at rated output 60 Hz  | cfm  | 
  | 494  | 
  | 
Exhaust temp. at muffler outlet  | °F  | 
  | 1,050  | 
  | 
  | 
  | 
  | 
  | 
  | 
ENGINE PARAMETERS  | 
  | 
  | 
  | 
  | 
Rated synchronous RPM  | 60 Hz  | 
  | 3600  | 
  | 
HP at rated KW  | 60 Hz  | 
  | 94  | 
  | 
  | 
  | 
  | 
  | |
POWER ADJUSTMENT FOR AMBIENT CONDITIONS | 
  | 
  | 
  | |
Temperature Deration  | 
  | 
  | 
  | 
  | 
3% for every 10 °C above - °C  | 
  | 25  | 
  | |
1.65% for every 10 °F above - °F  | 
  | 77  | 
  | |
Altitude Deration  | 
  | 
  | 
  | 
  | 
1% for every 100 m above - m  | 
  | 915  | 
  | |
3% for every 1000 ft. above - ft. | 
  | 3000 | 
  | |
  | 
  | 
  | 
  | 
  | 
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with