Installation Manual VMH SerieS Heat Controller, Inc.
6
INSTALLATION INSTRUCTIONS
Fig.4
Correct orientation
of Installation Plate
Wall
Indoor Outdoor
3/16”-1/4”(5-7mm)
Fig.6
Fig.5
Indoor unit installation(wall-mounted type)
2. Dri ll a hole i n the wal l
Note:
1. Fit th e Insta llati on Plat e
1. Fit the installation plate horizontally
on stru ctura l parts ( studs ) of the wa ll with
spaces around the installation plate.
2. If the w all is ma de of bri ck, con crete
or the li ke, dri ll five o r eight 3/16”(5mm)
diameter holes in the wall.Insert Clip anchor
for appropriate mounting screws.
3. Fit th e insta llati on plat e on the wa ll
with fi ve to eight type “A” screws.
1. Fit the Installation Plate and drill
holes in the wall according to the
wall structure and corresponding
mounting points on the installation
plate.
2. The In stall ation P late ma y be
slightly different according to the
different models of indoor unit.
3. Use a st ud find er to loc ate the s tuds
to prevent any unnecessary damage
to the wa ll.
1. Determine hole positions according
to the di agram d etail ed in Fig .5. Dri ll
one (1) h ole 2-9/16”(¦65mm) slanting slightly
to outd oor sid e see Fig . 6.
2. Always use wall hole conduit when
drill ing met al grid , metal p late or t he like .
3. Connective Pipe and Drainage
Installation
1. Run the drain hose sloping downward.
Do not install the drain hose as
illustrated in Fig.7.
Drainage
Fig.7
Do not block water flow by a rise.
Do not put the end of
drain hose into water.
Indoor unit outline Installation plate
292
Right rear side
refrigerant
pipe hole ¦2-9/16”(65)
Left rear side
refrigerant
pipe hole ¦2-9/16”(65)
4.75”(120mm) or
more to wall
4.75”(120mm) or
more to wall
A
45
D
C
45
A
1.75”(45)
B
Right rear side
refrigerant
pipe hole ¦2-9/16”(65)
Installation plate
Indoor unit outline
Left rear side
refrigerant
pipe hole ¦2-9/16”(65)
6”(150mm) or more to ceiling
4.75”(120mm) or
more to wall
4.75”(120mm) or
more to wall
Model A) A: 27.95”(7-10mm), B:9.84”(250mm), C:3.94”(100mm), D: 4.33”(110mm)
Model B) A: 31.10”(790mm), B:10.43”(265mm), C:3.94”(100mm), D: 5.91”(150mm)
1.75”(45)
CD
6”(150mm) or more to ceiling
4.75”(120mm) or
more to wall
Right rear side
refrigerant
pipe hole ¦2-9/16”(65)
1.75”(45)
1.75”(45)
Left rear side
refrigerant
pipe hole ¦2-9/16”(65)
4.75”(120mm) or
more to wall
6”(150mm) or more to ceiling
Model A) A: 27.95”(7-10mm), B:9.84”(250mm), C:3.94”(100mm), D: 4.33”(110mm)
Model B) A: 31.10”(790mm), B:10.83”(265mm), C:3.94”(100mm), D: 3.35”(85mm)
Model C) A: 33.46”(850mm), B:11.42”(290mm), C:3.94”(100mm), D: 4.53”(115mm)
Model A) A: 36.22”(920mm), B:11.54”(293mm), C:5.91”(150mm), D: 7.28”(185mm)
Model B) A: 39.17”(995mm), B:11.54”(293mm), C:5.91”(150mm), D: 7.87”(200mm)
Model C) A: 33.46”(850mm), B:12.01”(305mm), C:5.91”(150mm), D: 5.71”(145mm)