Hitachi X200 Series instruction manual DIP Switch Introduction

Models: X200 Series

1 286
Download 286 pages 46.11 Kb
Page 44
Image 44

25

DIP Switch Introduction

The inverter has internal DIP switches, located at the middle of the logic connectors as shown below. This selection provides an introduction, and refers you to other chapter that discuss the DIP switch in depth.

485

OPE

SW7

SW8

ON

OFF

Inverter Mounting and installation

SW7

485

OPE

SW8

ON

OFF

The 485/OPE (RS485/Operator) DIP switch configures the inverter’s RS485 serial port. You can use either the inverter’s integrated keypad or the OPE (OPE SR-mini) connected via a cable to the serial port. In this case the SW7 should be set OPE (default set). Inverter control via a ModBus network communication requires the “485” setting. See “Connecting the Inverter to ModBus” on page B-3for more details.

The SW8 is for the emergency signal input. If you turn this DIP switch ON, the inverter is ready to receive emergency signal from the dedicated terminal #3. Inverter shuts off the output by means of pure hardware when a signal is given to the terminal. It complies to EN954-1, category 3. Each signals related to this emergency input must be in accordance with the norm. Additionally, the logic input terminal assign will be changed automatically if the SW8 is made ON. See “Safe Stop” on page 4-32for more details.

Page 44
Image 44
Hitachi X200 Series instruction manual DIP Switch Introduction