IQ8Wireless transponder for wall mounting

36 FB 798941 / 10.06

10.4 Stand-alone operation

In the stand-alone mode the transponder operates with no need of any further connections to
a fire alarm system. To connect local arm devices the relay common fire (Sa-Feu) and/or
common fault (Sa-Stör) may be used.
A fault message may be transmitted via the common fault relay to, e.g. a supervising system
or an authorized person.
Reset
To reset the transponder connect an external reset button (refer to c) or a relay contact. In
this case a voltage of 9 to 30 V DC must be switched for at least 1 second at the input (input +/-)
of the IQ8Wireless transponder.
-+
9 V DC - 30 V DC
Reset
J1
J2
CNONC CNCNO
R-

+Eing -

+UB
P
1
Jumper J1 + J2
removed
-

+-

IN OUT

+

Sa-Feuer
Common fire Sa-Stör
Common fault
Fig. 21: Required wiring for the stand–alone operation
Connection data
External power supply 9 V DC to 30 V DC
Jumper J1 and J2 removed
Reset time = 0.2 to 3 seconds