Fig. 8. Wiring layout for one doubly terminated daisy-chain LonWorks segment.

Cable Termination

The FTT network segment requires termination for proper

data transmission performance. Use a 209541B

Termination Module to connect two of the three termination

module wires to the LonWorks Bus terminals.

Singly Terminated Network Segment

In a singly terminated topology segment, only one

termination is required and can be placed anywhere on the

segment. Singly terminated segments use the yellow and

brown wires. Mount the termination modules on the

appropriate terminals as shown in Fig. 9.

C1 C2 C3 C4 C5
EB EB XTTASAS
ORANGE
BROWN YELLOW PART NO. 209541B
TERMINATION MODULE
M16202

Fig. 9. Singly terminated LonWorks Bus termination

module.