Specific Parameters for Intrinsic Safety
Special conditions for safe use,
Intrinsic Safety (X)
Specific Parameters for Flameproof Installation
Special conditions for safe use, Flameproof Installation
Field wiring terminals, (+ , | Ui = 30 V, | Ii = 100 mA, | Pi = 1.2 W |
Without local analog meter, ME: | Ci = 4.2 nF, | Ri = 0, | Li = 0 |
With local analog meter, ME: | Ci = 4.2 nF, | Ri = 0, | Li = 150 µH |
With local smart digital meter, SM: | Ci = 4.2 nF, | Ri = 0, | Li = 0 |
|
|
|
|
The pressure transmitter is an intrinsically safe apparatus that can be installed in potentially explosive atmospheres.
The power terminals (+,
The electrical parameters (U, I, and P) of the associated apparatus connected to the power terminals (+,
Ui ≤ 30V
Ii ≤ 100 mA
Pi ≤ 1,2 W
Ambient temperature: - 50ºC to 93ºC
NOTE:
Temperature classifications:
IS (ia) 4 – 20 mA / DE | Flameproof (d) |
T4 up to Ta ≤ 93ºC | T5 up to Ta ≤ 93ºC |
T5 up to Ta ≤ 85ºC | T6 up to Ta ≤ 78ºC |
T6 up to Ta ≤ 70ºC |
|
|
|
Enclosure classification: IP 66/67, Type 4X
Power supply to field wiring terminals, (+,
Output Signal:
Ambient operating temperature: - 50 to 93ºC
NOTE:
10/04 | 5 of 10 |