4.1 Mounting ST 3000 Transmitter, Continued

Remote seal mounting

ATTENTION

Use the procedure in Table 10 to mount a remote diaphragm seal transmitter model. Figure 10 shows a typical installation for a remote diaphragm seal transmitter for reference.

Mount the transmitter flanges within the limits stated here for the given fill-fluid in the capillary tubes with a tank at one atmosphere.

IF the fill fluid is…

THEN mount the flange…

 

 

Silicone DC 200 Oil

no greater than 22 feet (6.7 meters)

 

below the transmitter

Silicone DC 704 Oil

no greater than 19 feet (5.8 meters)

 

below the transmitter

Chlorotrifluorethylene

no greater than 11 feet (3.4 meters)

 

below the transmitter.

NOTE: The combination of tank vacuum and high pressure capillary

 

 

 

head effect should not exceed 9 psi (300 mm Hg) absolute.

Table 10

 

 

Mounting Remote Diaphragm Seal Transmitter

 

 

 

 

 

 

 

 

 

 

 

 

 

Step

 

 

 

 

Action

 

 

 

 

 

 

 

 

 

 

 

 

1

Mount transmitter at a remote distance determined by length of

 

 

 

 

capillary tubing.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

If Transmitter Model

 

Then Connect Remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number is…

 

Seal on…

 

 

 

 

 

 

 

STR93D or STR12D

 

high pressure (HP) side of

 

 

 

 

 

 

 

 

 

 

transmitter to lower flange

 

 

 

 

 

 

 

 

 

 

mounting on tank wall for

 

 

 

 

 

 

 

 

 

 

variable head H1.

 

 

 

 

 

 

 

STR13D

 

low pressure (LP) side of

 

 

 

 

 

 

 

 

 

 

transmitter to lower flange

 

 

 

 

 

 

 

 

 

 

mounting on tank wall for

 

 

 

 

 

 

 

 

 

 

variable head H1.

 

 

 

 

 

 

 

 

 

 

 

 

 

ATTENTION

On insulated tanks, remove enough insulation to

 

 

 

 

 

 

 

 

 

 

accommodate the flange extension.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Continued on next page