4.3 Wiring ST 3000 Transmitter, Continued
Conduit seal
WARNING
Transmitters installed as explosionproof in a Class I, Division 1, Group A Hazardous (Classified) Location in accordance with ANSI/NFPA 70, the US National Electrical Code (NEC), require a “LISTED” explosionproof seal to be installed in the conduit, within 18 inches of the transmitter.
Transmitters installed as explosionproof in a Class I, Division 1, Group B, C or D Hazardous (Classified) Locations do not require an explosionproof seal to be installed in the conduit.
NOTE: Installation should conform to all national and local electrical code requirements.
When installed as explosionproof in a Division 1 Hazardous Location, keep covers tight while the transmitter is energized. Disconnect power to the transmitter in the
When installed as nonincendive equipment in a Division 2 Hazardous Location, disconnect power to the transmitter in the
Continued on next page
2/05 | ST 3000 Release 300 Installation Guide | 43 |