T8511G,R MICROELECTRONIC HEAT PUMP THERMOSTATS

Em HeatOffCool Auto Only

Heat Cool

OnAuto

System Fan

Room

Outdoor

Em Ht Temporary Setting

Wait

%Humid

Aux Ht Remote

Repl

Batt

M4844
INSTALLER SYSTEM-TEST
Use the Installer System-Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system-tests.
To start the system-test:
NOTE: The minimum off time for compressors is
bypassed during the Installer System-Test.
Press and hold the increase and decrease keys, at
the same time, until two zeros appear. All segments of the
LCD are displayed before the two zeros appear.
NOTE: Press and hold the increase and decrease
keys for three seconds to exit the system-test.
The system-test times out after five minutes
without any key presses.
Table 3. Tests Available in the Installer System-Test.
Refer to Table 4 for the directions and results of the
specific tests.
Test
Number System-Test Description
10-19 Heating equipment can be turned on and off
20-29 Emergency heat (select models) equipment
can be turned on and off
30-39 Cooling equipment can be turned on and off
40-49 Fan equipment can be turned on and off
60-69 System key or system switch position test
70-79 Thermostat information including date code
and software versions are displayed
Table 4. Installer System-Test Options.
aAvailable on select models.
bT8511R models with fixed emergency heat output will not respond to this key press.
(Continued)
Key To
Press Test
Number Description
Heating Equipment System-Test
i 10 Enter heating equipment system-test. (Set T8511R system switch to HEAT and fan switch to
AUTO.)
11 Stage-one heat comes on. The system fan is also energized.
12 Stage-two heat comes on. Stage-one heat and system fan remain on.
11 Stage-two heat turns off.
10 Stage-one heat and system fan turn off.
Emergency Heating Equipment System-Testa
i 20 Change from heating to emergency heating equipment system-test.
(Set T8511R system switch to EM. HT.)
b21 Emergency heat comes on. System fan also comes on.
b20 Emergency heat turns off. (Set T8511R system switch to OFF.)
Cooling Equipment System-Test
i 30 Change from heating or emergency heating to cooling equipment system-test.
(Set T8511R system switch to COOL.)
31 Stage-one cooling and system fan come on.
30 Stage-one cool and system fan turn off.
M6792
TEST NUMBER