TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
9 62-0273—05
INSTALLER SETUP NUMBERS, SETTINGS, AND TESTS (TABLE 4)
Configure Installer Setup
1. Press and release the System key.
2. Press System and Done keys simultaneously.
3. Hold keys for approximately five seconds, until the
screen changes.
4. When the display changes, release the System and
Done keys.
NOTE: See Table 4 for installer setup (ISU) numbers
and settings.
Installer System Tests
Use the Installer System Test section to test the heating,
cooling and fan. Refer to the latter portion of Table 4.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed
during Installer System Test
Avoid cycling compressor quickly.
IMPORTANT
Use Installer System Test to test heating, cooling
and fan. The setting chosen for System Type
(Installer Setup Number 0170) can prevent some
System Test Numbers from appearing.
Table 4. Installer Setup Menu.
Installer
Setup
Number
Installer Setup
Name
Default
Setting All Settings Notes
0120 Date (Year Upper) 20 20—21 Available year range: 2001 - 2178
0130 Date (Year Lower) 08 00-99 Available year range: 2001 - 2178
0140 Date (Month) 6 1-12
0150 Date (Day) 15 1-31 (Month Dependent)
0160 Schedule Options 4 0—Non-Programmable
4—Programmable
0170 System Selection 1 1—1H/1C Conv
2—1H w/o fan
3—1H with fan
4—1C
5—1H/1C HP
6—2H/1C HP
7—4 pipe Fan Coil
8—2 pipe Fan Coil
9—2 pipe Fan Coil w/ Aux
Heat
10—PTAC 1H/1C (Hi
speed, Lo speed Fan)
11—PTAC 2H/1C (Hi
speed, Lo speed Fan)
Relay Y is used for 2 pipe fan coil output relay.
0180 Heat Fan Operation 0 0—Fossil
1—Electric
Only shows up if conventional system with heat
stages and fan capability is selected (ISU 0170). If
heat pump is selected, fan defaults to electric. If
fan coil or PTAC modes are selected, fan defaults
to electric (does not show up).
0185 Pre-occupancy
Purge Duration
0 0—no duration
1—one hour
2—two hours
3—three hours
Shown only if system has fan and schedule is
programmable (ISU 0160).
Pre-occupancy purge is enabled by a nonzero
duration.
0190 Reversing Valve
O/B
0 0—O (O/B On Cool)
1—B (O/B On Heat)
Only shown if heat pump or PTAC system is
selected.
0220 Cycles Per Hour
(CPH) for first stage
cooling/compressor
3 1-6 Only shown if system has cool stages (ISU 0170).
Shown for heat pump, fan coil, PTAC, and
conventional cooling stages.
0240 CPH for first stage
heat
5 1-12 Only shown if system is conventional with heat
stages, 4 pipe fan coil, 2 pipe fan coil (ISU 0170).
0270 CPH for Em Heat 9 1-12 Only shown if HP with rehea t, 2 pipe fan coil with
reheat, and PTAC with reheat (ISU 0170).
0280 Continuous
Backlight
0 0—No
1—Yes
Always shown; however, if AC power is not
present, the option is overridden and normal
backlight operation occurs.