
Because of its common mode rejection, a differential oscilloscope displays only the difference in signal between its two vertical input terminals, thus ignoring the effects of any common mode signal produced by the difference in the ac potential between the power supply case and scope case. Before using a differential input scope in this man- ner, however, it is imperative that the common mode rejection capability of the scope be verified by shorting together its two input leads at the power supply and observing the trace on the CRT. If this trace is a straight line, then the scope is properly ignoring any common mode signal present. If this trace is not a straight line, then the scope is not rejecting the ground signal and must be realigned in accordance with the manufacturer’s instructions until proper common mode rejection is attain- ed.
a. Connect oscilloscope or RMS voltmeter as shown in Figures
b. Turn CURRENT controls fully clockwise. c. Adjust VOLTAGE controls until front panel
meter indicates maximum rated output voltage. d. The observed ripple should be less than
the following:
6259B, 6260B, 6261B
6268B, 6269B
is generally not acceptable for measuring spikes; a differential oscilloscope is necessary. Further- more, the measurement concept of Figure
1.As shown in Figure
2.Impedance matching resistors must be in- cluded to eliminate standing waves and cable ring- ing, and capacitors must be inserted to block the dc current path.
3.The length of the test leads outside the coax is critical and must be kept as short as pos- sible; the blocking capacitor and the impedance matching resistor should be connected directly from the inner conductor of the cable to the power supply terminals.
4.Notice that the shields of the power sup- ply end of the two coax cables are not connected to the power supply ground, since such a connection would give rise to a ground current path through the
TM
Figure
coax shield, resulting in an erroneous measurement.
5.Since the impedance matching resistors constitute a
Definition: The time "X" for the output voltage recovery to within "Y" millivolts of the nominal output voltage following a "Z" amp step change in load current, where: "Y" is specified as 10mV, the nominal output Voltage is defined as the dc level ‘halfway between the static output voltage before and after the imposed load change, and "Z" is the specified load current change of S amps or the full load current rating of the supply, whichever is less.