Power and Signal Distribution
Table
Table
|
| AC Range or | Min. |
|
|
|
|
| Current | Max. | Surge | Max. | |
|
| DC Regulation | Loading [1] | Current | Current [2] | Ripple |
|
|
|
|
|
| |
Input voltage: |
|
|
|
|
| |
115 | VAC | |||||
230 VAC |
|
|
|
| ||
|
|
|
|
|
| |
Line Frequency | ||||||
|
|
|
|
|
| |
Input (AC) Current Requirement | 4 A rms | |||||
(100 VAC rms @ 60 Hz) |
|
|
|
|
| |
|
|
|
|
|
| |
Output voltage (VDC): |
|
|
|
|
| |
+12 | Vmain | 11.62 to 12.57 | 0.5 A | 16 A | 18 A | 120 mV |
+12 | Vcpu | 11.62 to 12.57 | 1 A | 16 A | 18 A | 120 mV |
+12 | Vsb (aux) | 11.06 to 11.74 | 0.1 A | 1.3 A | 1.5 A | 120 mV |
0 A | 0.15 A | 0.5 A | 120 mV | |||
|
|
|
|
|
|
|
NOTES:
Total continuous power should not exceed 240 watts. Total surge power (<10 seconds w/duty cycle < 5 %) should not exceed 265 watts.
[1]The minimum current loading figures apply to a PS On start up only.
[2]Maximum surge duration for +12Vcpu is 1 second with
Table
Table
|
| AC Range or | Min. |
|
|
|
|
| Current | Max. | Surge | Max. | |
|
| DC Regulation | Loading [1] | Current | Current [2] | Ripple |
|
|
|
|
|
| |
Input voltage: |
|
|
|
|
| |
115 | VAC | |||||
230 VAC |
|
|
|
| ||
|
|
|
|
|
| |
Line Frequency | ||||||
Input (AC) Current Requirement | 5.5 A rms | |||||
(100 VAC rms @ 60 Hz) |
|
|
|
|
| |
|
|
|
|
|
| |
Output voltage (VDC): |
|
|
|
|
| |
+12 | Vmain | 11.62 to 12.57 | 0.5 A | 16 A | 18 A | 120 mV |
+12 | Vcpu | 11.62 to 12.57 | 1 A | 16 A | 18 A | 120 mV |
+12 | Vsb (aux) | 11.06 to 11.74 | 0.1 A | 1.3 A | 1.5 A | 120 mV |
0 A | 0.15 A | 0.5 A | 120 mV | |||
|
|
|
|
|
|
|
NOTES:
Total continuous output power should not exceed 320 watts.
[1]Minimum loading requirements must be met at all times to ensure normal operation and specification compliance.
[2]Maximum surge duration for +12Vcpu is 1 second with
www.hp.com | Technical Reference Guide |