AC Controls
Manual Motor Starter Protector
General / Dimensions
Type 3VU13 Manual Motor Starter Protector
Siemens 3VU13 is a
Features
J
3VU13 Enclosure Dimensions
JThe Manual Starters Meet or Exceed Requirements of NEMA, EEMAC, UL, CSA, IEC, VDE and Other International Standards. The
JMotor Ratings — Up to 25 HP 3- Phase and 10 HP Single Phase.
JClass 10 Adjustable Ambient Compensated Overload Protection.
JPhase Loss Sensitivity.
JUndervoltage Protection — UV trip module may be added in field.
JShunt Trip Module is also field adda- ble.
JAvailable in Open Styles, NEMA 1 and 3R, watertight, dusttight, under table, and flush mount enclosures.
J1 NO and 1 NC Auxiliary Contacts Standard.
JGroup Installation - UL 508. The 3VU13 is suitable for Group Installation at 5kA 600 volts maximum with any fuse up to 1200 amperes or any inverse time circuit breaker up to 1200 amperes. The 3VU13 can be installed with or without Siemens con- tactors type 3TF2 or 3TF30 to 3TF34 in series. For higher interrupting rat- ings, consult Siemens.
Overlead and Magnetic Trip Tripping Characteristics
Table 15.10 | Technical Data |
|
| |
Manual Motor Starter Protector |
|
| ||
Type |
| 3VU13 | ||
Maximum Rated Continuous | 25 |
| ||
Current (Amperes) |
| |||
|
| |||
Rated Operating Voltage AC |
|
| ||
| 600V | |||
|
|
| ||
Ambient Temperature | 55 | |||
Compensation °C | ||||
|
| |||
Maximum Rated HP of |
|
| ||
|
| |||
| 5 |
| ||
| 7 1⁄2 | |||
| 15 |
| ||
| 20 |
|
15
Controls AC
CSI Section 16160 | Siemens Electrical Products and Systems | 289 |
| Specification Guide |
|