LCD Configuration and Status

Displaying the Frequency, Power, and Current Data

Select Meters on the Main Menu to view the frequency, power and current of either the main module or any of the other electronics modules.

Main Menu

Meters

This submenu provides information on virtual meters monitoring the UPS voltages. Scroll up and down through the menu using the Center button. If the words continue off the screen, scroll right and left to read the message. Press the Enter button to view selections. Table 3-5lists the options under the Meters menu.

Table 3-5: Main Module and Electronics Modules M1-M4 Meter Options

LCD Display

Explanation

Input Volts

The utility voltage

 

 

Output Volts

The voltage available at the UPS output receptacles

 

 

Input Frequency

The utility frequency in Hertz

 

 

Output Frequency

The frequency in Hertz available at the UPS output

 

receptacles

Output Power

❚❚❚❚❚❚❚❚❚❚❚❚ MM or Mx

The output power is shown in a bar graph. This example shows 120% load (overload). There are ten squares in front of the 100% line. Each represents a 10% load. The two squares past the line each represent 10% of overload (20% overload in all).

Output Power

In contrast, this display shows a 60% load.

 

 

❚❚❚❚❚❚------ MM or Mx

 

Battery Volts

The battery voltage

 

 

Input Current

The input current

 

 

HP Uninterruptible Power System R12000 XR Models User Guide