Troubleshooting

Table 5-1: Main Module and Electronics Modules M1-M4 Active Alarms continued

LCD Display

Possible Cause

Suggested Action

xAlarms

Internal

Communications

Failure

The UPS encounters an internal communication problem that is hindering its ability to successfully manage its activities and monitor the current electronics module status. The UPS will immediately transfer to Battery mode and issue the Low Battery alarm until communications are restored.

Switch to Maintenance Bypass mode, and contact Technical Support for assistance.

xAlarms

Inverter Contactor

Open

The UPS detects that an electronics module has timed out waiting for its load relay to close during a module hot-swap. The electronics module has failed to complete its startup sequence successfully. This alarm is accompanied by one or more alarms from the electronics module that indicates the root cause of the problem.

Select the Status option on the LCD menu. Scroll through and examine the additional alarms related to the failed electronics module for details on handling this condition.

x Alarms

At least one electronics module detects

Contact Technical Support for

 

a hardware failure in its inverter,

assistance.

Inverter Fault

generates this alarm, and subsequently

 

 

 

 

shuts down. The UPS may have

 

 

transitioned into Automatic Bypass

 

 

mode due to the failure, depending on

 

 

the load levels present at the time of

 

 

the failure.

 

 

This could be caused by a hardware

 

 

failure.

 

 

 

 

x Alarms

At least one electronics module

Reduce the load level to within UPS

 

generates this alarm when it has

operational limits. Initiate a Manual

Inverter Output

reached its maximum operating output

Bypass Recovery if the UPS remains in

Over Current

hardware current limits, as defined in

Bypass mode for more than

 

 

the EEPROM. The module has shut

30 seconds. See the LCD panel to

 

down to protect itself and the load from

determine which electronics module

 

damage. The UPS may have

generated the alarm.

 

transitioned into Automatic Bypass

If the UPS was operating within its

 

mode due to the failure, depending on

 

supported load limits when the problem

 

the load levels present at the time of

 

occurred, or if the problem persists,

 

the failure and the number of modules

 

contact Technical Support for

 

affected.

 

assistance.

 

 

 

 

 

 

 

continued

HP Uninterruptible Power System R12000 XR Models User Guide