Chapter 55. xSeries rack power configurator 481
Country-specific considerations: USA, Canada, parts of Latin America,
Taiwan
Power Load Capacity
Part
Number
PlugType SourceCircuit
(singlephase 50/60Hz)
PDUOutput
(singlephase 50/60Hz)
32P1761 NEMAL5-15P100-127Vac,15a six 100-127Vac, NEMA 5-15R
receptacles,shared12a
NEMAL5-20P 100-127Vac,20a seven100-127Vac,shared15a
NEMAL6-20P 200-240Vac,20a seven200-240Vac,shared15a
32P1736
Part
Number
PlugType SourceCircuit (50/60Hz) PDUOutput
(singlephase 50/60Hz)
32P1751NEMA L5-30P 100-127Vac,30a,
single-phase
three100-127Vac,20a each, shared
24a
32P1766NEMA L6-30P 208Vac,30a,single-phase
line-to-linewith ground
three208Vac,20a each, share
d24a
32P1767IEC 309-2P+G 208Vac,60a,single-phase
line-to-linewith ground
three208Vac,20a each, shared
48a
Part
Number
PlugType SourceCircuit(50/60Hz) PDUOutput
(singlephase 50/60Hz)
73P5855IEC 309 2P+G 208Vac,60a,single-phase
dedicatedcircuit
twelve208Vac,16a each, shared
48a
73P5847IEC 309 3P+G 208Vac,60a,three-phase
deltadedicated circuit
twelve 208Vac,16a each, shared
28aper four outlet phase group
RackPDUs
Front-endPDUs
HighDensity PDUs
EnterprisePDUs
Part
Number
PlugType SourceCircuit(50/60Hz) PDUOutput
(singlephase 50/60Hz)
26K4246 NEMA L6-30P 208Vac,30a,single-phase
dedicatedcircuit
twelve208Vac,10a each, shared
24a
26K4242IEC 309 2P+G 208Vac,60a,single-phase
dedicatedcircuit
twelve 208Vac,10a each, shared
48a
26K4244IEC 309 3P+G 208Vac,60a,three-phase
deltadedicated circuit
twelve 208Vac,10a each, shared
28aper four outlet phase group
26K4256IEC 309 2P+G 208Vac,60a,single-phase
dedicatedcircuit
six208Vac,16a each, shared 48a
26K4258IEC 309 3P+G 208Vac,60a,three-phase
deltadedicated circuit
six 208Vac,16a each, shared 28a
pertwo outlet phase group
(2)Line Cords: Rack PDU
(5)Line Cords: Front-end
PDU
PowerCables:
(1)Device to Rack PDU or Enterprise C13 PDU power cable
IECC13 to C14, 10/15a cable
typical: 36L8886 (2.8m)
requirement:C14 plug, long enough to reach
availableoption: 94G7448(14ft)
(2)Rack PDU to wall line cord
IECC19 to country-specific connector,16/20a, 14ft (4.3m)
(3)Rack PDU to UPS power cable
IECC19 to C20, 16/20a
00N7700(2m)
providedwith 37L6861APC SU-5000RMB
(4)Rack PDU to Front-end PDU power cable
IECC19 to C20, 16/20a
00N7698(1m) provided with the NetBAYFront-end PDUs
00N7700(2m) provided with the DPI Front-end PDUs
(5)Front-end PDU to wall line cord
hardwiredto country-specific connector,30/32a, 60/63a, 8.2ft
(2.5m)
(7)Device to High Density PDU power cable
IECC19 to C20, 16/20a, 2.5m
(8)Enterprise PDU to wall line cord
hardwiredor pluggable to country-specific connector,30/60a, 14ft
(4.3m)
(9)High Density PDU to wall line cord
hardwiredor plugugable to country-specific connector,60a, 8.2ft
(2.5m)
(10)Device to FE-, E-, or HD-PDU power cable
IECC13 to C20, 10/15a cable
option: 23K4809 9ft (2.8m)
(9)Line Cords:High Density PDU
(8)Line Cords:Enterprise PDU