8NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Alcove
Option 1
Alcove
Option 3
Alcove
Option 2
Carpet Leg
1-1/2” (38mm)
Maximum
Corner Installation
ClearanCes to Combustibles
Minimum clearances to combustible materials shown here
are in inches (millimeters). See page 7 for pipe clearances.
Parallel Installation
floor proteCtion
A non-combustible hearth pad is not required. This stove
may be installed on a combustible surface as long as the
combustible material (such as carpeting) does not extend
1-1/2” vertically above the bottom of the legs (see Figure
6). Also, the floor beneath the stove must be stable, level,
hard, and strong enough to support the stove without a
tipping hazard.
Leg on Combustible
90˚
4"
(102mm)
10-5/8"
(270mm) 13-7/8"
(352mm)
4"
(102mm)

Combustible Wall

Combustible Wall
4"
(102mm)
15-1/4"
(387mm)
4"
(102mm)
Combustible Wall

Combustible Wall

Figure 4
Figure 5
Figure 6
alCove dimensions
The minimum width between alcove side walls is 30-1/2”
(775mm). The glass door lifts up to access the firebox on the
stove. Therefore, if the stove is to be installed in an alcove,
the alcove needs to be constructed to allow for removal of
the glass door. Option 1: The maximum alcove depth is
15” (381mm) (maintaining a 4” [102mm] rear clearance
the stove will be positioned partly into the room) and the
remaining minimum dimensions to combustibles are as
shown in the Option 1 drawing below. Option 2: The alcove
is 43” (1092mm) high to provide sufficient space to remove
the door. The maximum depth of the alcove is 24” (610mm).
Option 3: Should an alcove depth from 2 feet (.61M) to 4
feet (1.22M)be desired then the minimum alcove height is
54” (1372mm). Access to the stove’s controls should be
considered when determining the alcove size.
33”
838mm
15”
381mm
40”
1016mm
42”
1067mm
30-1/2”
775mm
43”
1092mm
24”
610mm
30-1/2”
775mm
30-1/2”
775mm
54”
1372mm
48”
1219mm
Figure 7
Figure 8
Figure 9