© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
ES58-2_DBL_LST_EN_0805.PDF • PAGE 1
ABuilding Safety. Building Security.

Safety Barrier

ES58-2

Description
Specifi cations
The Safety Barrier ES58-2 for the galvanic isolation of
the detectors in the hazardous area serves for the de-
sign of an intrinsically safe electric circuit. The plastic
surface-mount housing allows to mount the safety bar-
rier near the hazardous area.
The built-in zener barrier limits the current and the vol-
tage of the detector line, as well as the electric energy
stored in the intrinsically safe circuit. The maximum
number of detectors depends on the country-specifi c
regulations and can be found in the Connection of De-
tectors.
Due to the galvanic isolation, the earth leakage moni-
toring can remain activated in the fi re detection control
panel. Thus, the installation can also be monitored in
the hazardous area.
Allows to create intrinsically safe
circuits
Galvanic isolation of the detector line
voltage
Connection of intrinsically safe
detectors
Industrial plastic surface-mount case
• ATEX certifi ed
Ignition protection intrinsically safe
Ex classifi cation EEx ia llC
Operating voltage Supply through the detector line voltage
Quiescent current approx. 5mA
Ambient temperature -20°C to +60°C
Dimensions W × H × D 120 × 160 × 90 (mm)
Colour light grey, similar to RAL 7035
Weight 650g
Approval BASEEFA98ATEX7343
Order number 228003
Order name Safety Barrier/Conv. ES58-2