Selection and protection of a motor
4
PARAMETERS
4.8 Selection and protection of a motor
4.8.1 Motor protection from overheat (Electronic thermal relay function) (Pr. 9, Pr. 51)
*1 The parameters can be set when Pr. 160 User group read selection = "0" (Refer to page 190)
*2 When parameter is read using the FR-PU04, a parameter name different from an actual parameter is displayed.
(1) Electronic thermal relay function operation characteristic (THM)
Purpose Parameter that must be Set Refer to page
Motor protection from overheat Electronic thermal O/L relay Pr. 9, Pr. 51 107
Use the constant-torque motor Applied motor Pr. 71 111
Set the current of the electronic thermal O/L relay to protect the motor from overheat. This feature provides the
optimum protective characteristics, including reduced motor cooling capability, at low speed.
Parameter
Number Name Initial Value Setting Range
200V class (400V class) Description
9Electronic thermal
O/L relay
Rated inverter
current
02330 (01160) or less 0 to 500A Set the rated motor current.
03160 (01800) or more 0 to 3600A
51 *1 Second electronic
thermal O/L relay *2 9999
02330 (01160) or less 0 to 500A Valid when the RT signal is ON.
Set the rated motor current.
03160 (01800) or more 0 to 3600A
9999
Second electronic thermal O/L relay
invalid
[Electronic thermal relay function operation characteristic ( E.THM)] This function detects the overload (overheat) of the
motor and the inverter trips. (The operation
characteristic is shown on the left)
Set the rated current [A] of the motor in Pr. 9.
(If the motor has both 50Hz and 60Hz rating and
the Pr.3 Base frequency is set to 60 Hz, set the 1.1
times of the 60Hz rated motor current.)
Set "0" in Pr. 9 when you do not want to activate the
electronic thermal relay function, e.g. when using
an external thermal relay with the motor. (Note that
the output transistor protection of the inverter
functions (E.THT).)
When using the Mitsubishi constant-torque motor
1) Set "1" in Pr. 71. (This provides a 100%
continuous torque characteristic in the low-speed
range.)
2) Set the rated current of the motor in Pr. 9.
*1 When 50% of the inverter rated output current (current value) is
set in Pr. 9
*2 The % value denotes the percentage to the inverter rated
current. It is not the percentage to the motor rated current.
*3 When you set the electronic thermal relay function dedicated to
the Mitsubishi constant-torque motor, this characteristic curve
applies to operation at 6Hz or higher.
CAUTION
Protective function by electronic thermal relay function is reset by inverter power re set and reset signal input. Avoid
unnecessary reset and power-OFF.
When multiple motors are operated by a single inverter, protection cannot be provided by the electronic thermal relay function.
Install an external thermal relay to each motor.
When the difference between the inverter and motor capacities is large and the setting is small, the protective characteristics of
the electronic thermal relay function will be deteriorated. In this case, use an external thermal relay.
A special motor cannot be protected by the electronic thermal relay function. Use the externa l thermal relay.
120
Electronic thermal relay
function for transistor
protection
52.5% 105%
50 100 150
60
120
180
240
50
60
70
6Hz
20Hz
10Hz
6Hz
0.5Hz
30Hz or more*3
20Hz
10Hz
0.5Hz
Pr. 9 = 50% setting of
inverter rating*1.2
Pr. 9 = 100% setting
of inverter rating*1.2
(s) unit display in this range (min) unit display in
this range
Operation time (min)Operation time (s)
Characteristic when
electronic thermal relay
function for motor
protection is turned OFF
(When Pr. 9 setting is 0(A))
30Hz
or more*3
Inverter output current(%)
(% to the rated inverter current)
Operation range
Range on the right of
characteristic curve
Non-operation range
Range on the left of
characteristic curve