122
Function assignment of external
terminal and control
4.10 Function assignment of external terminal and control
4.10.1 Input terminal function selection (Pr. 178 to Pr. 189)
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190)
....Specifications differ according to the date assembled. Refer to page 400 to check the SERIAL number.
(1) Input terminal function assignment
Use Pr. 178 to Pr. 189 to set the functions of the input terminals.
Refer to the following table and set the parameters:
Purpose Parameter That Must be Set Refer to Page
Assign function to input terminal Input terminal function
selection Pr. 178 to Pr. 189 122
Set MRS signal (output shutoff) to NC
contact specification MRS input selection Pr. 17 124
Make the second function valid only
during constant speed operation.
RT signal function validity
condition selection Pr. 155 125
Assign start signal and forward/
reverse command to other signals
Start signal (STF/STR)
operation selection Pr. 250 126
Assign function to output terminal Output terminal function
assignment Pr. 190 to Pr. 196 128
Detect output frequency.
Up-to-frequency sensitivity
Output frequency detection
Speed detection hysteresis
Pr. 41 to Pr. 43, Pr. 50, Pr. 870 133
Detect output current. Output current detection
Zero current detection
Pr. 150 to Pr. 153, Pr. 166,
Pr. 167 135
Remote output function Remote output Pr. 495 to Pr. 497 137
Detect specified output power Pulse train output of output
power Pr. 799 138
Use these parameters to select/change the input terminal functions.
Parameter
Number Name Initial
Value Initial Signal Setting Range
178 STF terminal function selection 60 STF (forward rotation command)
0 to 8, 10 to 14, 16, 24, 25,
50, 51, 60, 62, 64 to 67, 70
to 72, 77, 78, 9999
179 STR terminal function selection 61 STR (reverse rotation command)
0 to 8, 10 to 14, 16, 24, 25,
50, 51, 61, 62, 64 to 67, 70
to 72, 77, 78, 9999
180 RL terminal function selection 0 RL (low-speed operation command)
0 to 8, 10 to 14, 16, 24, 25,
50, 51, 62, 64 to 67, 70 to
72, 77, 78, 9999
181 RM terminal function selection 1 RM (middle-speed operation command)
182 RH terminal function selection 2 RH (high spe ed operation command)
183 RT terminal function selection 3 RT (second function selection)
184 AU terminal function selection 4 AU (terminal 4 input se lection)
0 to 8, 10 to 14, 16, 24, 25,
50, 51, 62 to 67, 70 to 72,
77, 78, 9999
185 JOG terminal function selection 5 JOG (Jog operation selection)
0 to 8, 10 to 14, 16, 24, 25,
50, 51, 62, 64 to 67, 70 to
72, 77, 78, 9999
186 CS terminal function selection 6CS (selection of automatic restart
after instantaneous power failure)
187 MRS terminal function selection 24 MRS (output stop)
188 STOP terminal function
selection 25 STOP (start self-holding selection)
189 RES terminal function selection 62 RES (inverter reset)
Setting Signal
Name Function Related Parameters Refer to
Page
0RL
Pr. 59 = 0 (initial value) Low-speed operation command Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239 93
Pr. 59 0 *1 Remote setting (setting clear) Pr. 59 98