157
Operation selection at power failure
and instantaneous power failure
4
PARAMETERS
(3) Power failure stop function (Pr. 261 = "1, 21")
If power is restored during power failure deceleration, deceleration to a stop is continued and the inverter remains
stopped. To restart, turn OFF the start signal once, then turn it ON again.
At power failure when Pr. 261 = "21", inverter decelerates to stop automatically by adjusting the deceleration time to
make converter voltage (DC bus) constant. (The setting of Pr. 262 to Pr. 266 are invalid.)
(4) Operation continuation at instantaneous power failure function (Pr. 261 = "2, 22")
When power is restored during deceleration after an instantaneous power failure, acceleration is made again up to
the set frequency.
When this function is used in combination with the automatic restart after instantaneous power failure operation,
deceleration is available at a power failure and acceleration is available again after power restoration. When power
is restored after a stop by deceleration at an instantaneous power failure, automatic restart operation is performed
if automatic restart after instantaneous power failure has been selected (Pr. 57 "9999")
At power failure when Pr. 261 = "22", inverter decelerates to stop automatically by adjusting the deceleration time to
make converter voltage (DC bus) constant. If the power supply recovers, inverter accelerates again to the set
frequency.
The setting of Pr. 262 to Pr. 266 are invalid when Pr. 261 = "22".
REMARKS
When automatic restart after instantaneous power failure is selected (Pr. 57 "9999"), deceleration to stop function is invalid and the
restart after instantaneous power failure operation is performed.
When the power failure deceleration stop function is active (Pr. 261 = "1,
21"), the inverter will not start even if the power is turned ON with the
start signal (STF/STR) ON. After switching ON the power supply, turn
OFF the start signal once and then ON again to make a start.
.
During deceleration at
occurrence of power failure
During stop at
occurrence of
power failure
STF
Y46
Time
Turn OFF STF once to make acceleration again
Power
supply
Output frequency
Pr.261 = 1
During deceleration at
occurrence of power failure
Deceleration time: automatically adjusted
During stop at
occurrence of
power failure
STF
Y46
Time
Turn OFF STF once to make acceleration again
Power
supply
Output frequency
Pr.261 = 21
STF
Power supply
Y46
Not started as inverter
is stopped due to power
failure
ON
OFF ON
Output
frequency
Time
ON
IPF
Power
supply
Time
Output
frequency
Y46
During deceleration
at occurrence of
power failure Reacceleration*
When power is restored during
deceleration at occurrence of
power failure
Pr. 261 = 2, 22
* Acceleration time depends on Pr. 7 (Pr. 44 ).
During power failure
Power
supply
Output
frequency
Y46
During deceleration
at occurrence of
power failure
Automatic restart
after instantaneous
power failure
Reset time + Pr.57
Pr.261 = 2, 22, Pr.57 9999When used with automatic restart
after instantaneous power failure
Time