4.18 Selection of operation mode and operation location
4.18.1 Operation mode selection (Pr. 79)
The above parameters can be changed during a stop in any operation mode.
* The priorities of the frequency commands when Pr. 79 = "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog
input (AU) > digital input from the operation panel".
Purpose Parameter that must be set Refer to page
Operation mode selection Operation mode selection Pr. 79 195
Started in network operation mode Operation mode at power ON Pr. 79, Pr. 340 203
Selection of operation location
Selection of start command source, speed
command source and operation location
during communication operation
Pr. 338, Pr. 339,
Pr. 550, Pr. 551 204
Used to select the operation mode of the inverter.
Mode can be changed as desired between operation using external command signals (external operation), operation
from the PU (FR-DU07/FR-PU04/FR-PU07), combined operation of PU operation and external operation (external/PU
combined operation, and network operation (when RS-485 terminals or a communication option is used).
Parameter
Number Name Initial
Value
Setting
Range
79 Operation mode selection 0 0 to 4, 6, 7
POINT
• Use the simple setting mode to set Pr. 79 in simple steps. (Refer to page 60)
Pr.79
Setting
Description LED Indication
: OFF : ON
Refer
to
0
Use external/PU switchover mode (press to switch between the PU and External
operation mode.
At power ON, the inverter is in the External operation mode.
PU operation mode
External operation mode
NET operation mode
198
1
Operation mode Frequency command Start command
PU operation mode
198
PU operation mode (fixed)
Setting by the operation
panel (FR-DU07) and PU
(FR-PU04/FR-PU07)
Input by and on
PU (FR-DU07/FR-PU04/
FR-PU07)
2
External operation mode (fixed)
The operation can be
performed by switching
between the External and NET
operation modes.
External signal input (from
terminal 2, 4, and 1, JOG,
multi-speed selection, etc.)
External signal input (from
terminal STF and STR)
External operation mode
NET operation mode 198
3External/PU combined
operation mode 1
PU (FR-DU07/FR-PU04/FR-
PU07) setting or external
signal input (multi-speed
setting, across terminals 4
and 5 (valid when AU signal
turns ON)). *
External signal input
(terminal STF, STR) 199
4External/PU combined
operation mode 2
External signal input
(Terminal 2, 4, 1, JOG,
multi-speed selection, etc.)
Input by and on
PU (FR-DU07/FR-PU04/
FR-PU07)
199
6
Switchover mode
Switch among PU operation, External operating, and NET operat ion while keeping the
same operating status.
PU operation mode
External operation mode
NET operation mode
200
7
External operation mode (PU operation interlock)
X12 signal ON: Operation mode can be switched to the PU operation mode.
(output stop during external operation)
X12 signal OFF: Operation mode cannot be switched to the PU operation mode.
200
REMARKS
If switching of the operation mode is invalid even though Pr. 79 is set, refer to page 351.