327
Initial value change list
4
PARAMETERS
4
PARAMETERS
4.28 Initial value change list
Displays and sets the parameters changed from the initial value.
.......The specification differ according to the manufac ture date. Refer to page 400 and check the SERIAL.
Operation Display
1. Screen at powering ON
The monitor display appears.
2.Press to choose the PU operation mode.
PU indication is lit.
3.Press to choose the parameter setting
mode.
PRM indication is lit.
(The parameter number read previously appears.)
4.Turn until appears.
5.Pressing changes to the initial value
change list screen.
6.Turning displays the parameter number
changed.
Press to read the currently set value.
Turn and press to change the
setting
(refer to step 6 and 7 on page 61)Flicker ··· Frequency setting complete!!
Turn to read another parameter.
The display returns to after all
parameters are displayed.
7.Pressing in status returns to
the parameter setting mode.
Turning sets other parameters.
Pressing displays the change list again.
REMARKS
Calibration parameters (C0 (Pr. 900) to C7 (Pr. 905), C42 (Pr. 934) to C45 (Pr. 935)) are not displayed even they are changed from
the initial settings.
Only simple mode parameter is displayed when simple mode is set (Pr. 160 = 9999 (initial value))
Only user group is displayed when user group is set (Pr. 160 = "1").
Pr. 160 is displayed independently of whether the setting value is changed or not.
Parameters referred to
Pr. 160 User group read selection Refer to page 190
C0 (Pr. 900) CA terminal calibration Refer to page 149
C2 (Pr. 902) to C7 (Pr. 905) (Frequency setting bias/gain parameter) Refer to page 177
C42 (Pr. 934) to C45 (Pr. 935) (PID control) Refer to page 261
PU EXT NET