58
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
2 Overview (Sequence Program)
2.7 Types and Setting of Parameters
2) FX3G PLCs
*1. This area can be set only in FX3U/FX3UC PLCs.
*2. This area can be set only in FX3G PLCs.
*3. X000 to X007 in the FX3U-16M, FX3UC-16M and 14-point type FX3G PLCs
X000 to X014 in 24-point type FX3G PLCs
Set item Contents of setting Setting range
Battery less mode*1
Select this to operate the PLC without using the battery.
When a check mark is put here, the battery error indicator lamp is automatically
turned off and devices in the latched (battery backed) area are automatically
cleared.
Battery mode*2 Select this item to operate the PLC with the battery.
MODEM initialized Set this item to automatically initialize a connected modem when the PLC power
is turned ON.
RUN terminal input Set this item to use an input terminal (X) to switch the PLC between STOP and
RUN.
None
X000 to X017*3