Programming Manual - Basic & Applied Instruction Edition
30 External Device Communication (Inverter Communication) – FNC270 to FNC274
30.3 FNC272 – IVRD / Inverter Parameter Read
2. Related devices
→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.
*1. Cleared when the PLC mode switches from STOP to RUN.
*2. Initial value: -1
Cautions
→ For other cautions, refer to the Data Communication Edition manual.
• It is not permitted to use an RS (FNC 80)/RS2 (FNC 87)/FLCRT (FNC300)/FLDEL (FNC301)/FLWR (FNC302)/
FLRD (FNC303)/FLCMD (FNC304)/FLSTRD (FNC305) instruction and an IVCK (FNC270)/IVDR (FNC271)/
IVRD (FNC272)/IVWR (FNC273)/IVBWR (FNC274) instruction for the same port.
• Two or more inverter communication instructions (FNC270 to FNC274) can be driven for the same port at the same
time.
PLC applicable version
The table below shows PLC versions applicable to each inverter.
Number Description Number Description
ch1 ch2 ch1 ch2
M8029 Instruction execution complete D8063 D8438 Error code of serial communication error
M8063 M8438 Serial communication error D8150 D8155 Response wait time in inverter communication
M8151 M8156 Inverter communicating*1 D8151 D8156 Step number in inverter communication*2
M8152 M8157 Inverter communication error*1 D8152 D8157 Error code of inverter communication
error*1
M8153 M8158 Inverter communication error
latch*1 D8153 D8158 Latch of inverter communication error
occurrence step*2
M8154 M8159 IVBWR instruction error*1 D8154 D8159 IVBWR instruction error parameter number*2
PLC FREQROL-V500/F500/A500/E500/S500 FREQROL-F700/A700 FREQROL-E700/D700
FX3G Ver.1.10 or later
FX3U Ver.2.20 or later Ver.2.32 or later
FX3UC Ver.1.00 or later Ver.2.20 or later Ver.2.32 or later