831
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
37 Operation of Special Devices (M8000 -, D8000 -)
37.1 Special Device List (M8000 -, D8000 -)
31
FNC275-FNC279
Data
Transfer 3
32
FNC280-FNC289
High Speed
Processing 2
33
FNC290-FNC299
Extension File
Register
34
FNC300-FNC305
FX
3U
-CF-ADP
35
SFC•STL
Programming
36
Interrupt
Function
37
Special Device
38
Error Code
A
Version Up
Information
B
Execution Times
Timing Clock (Refer to Section 24.3 for details.) and Positioning [FX
3G
, FX
3U
and FX
3UC
PLCs]
(Refer to Positioning Control Edition for
details.)
[M]8330 DUTY (FNC186) instruction: Timing clock output 1 33*1 D8330 – – –
[M]8331 DUTY (FNC186) instruction: Timing clock output 2 33*1 D8331 – – –
[M]8332 DUTY (FNC186) instruction: Timing clock output 3 33*1 D8332 – – –
[M]8333 DUTY (FNC186) instruction: Timing clock output 4 33*1 D8333 – – –
[M]8334 DUTY (FNC186) instruction: Timing clock output 5 33*1 D8334 – – –
[M]8335 Not used – – –––– –
M 8336*2 DVIT (FNC151) instruction:
Interrupt input specification function enabled 33*3 D8336 – – –
[M]8337 Not used – – –––– –
M 8338*2 PLSV (FNC157) instruction:
Acceleration/deceleration operation 3 3 3*1 –––– –
[M]8339 Not used – – –––– –
[M]8340 [Y000] Pulse output monitor
(ON: BUSY/ OFF: READY)
3 3 3 –––– –
M 8341*2 [Y000] Clear signal output function enable 3 3 3 –––– –
M 8342*2 [Y000] Zero return direction specification 3 3 3 –––– –
M 8343 [Y000] Forward limit 3 3 3 –––– –
M 8344 [Y000] Reverse limit 3 3 3 –––– –
M 8345*2 [Y000] DOG signal logic reverse 3 3 3 –––– –
M 8346*2 [Y000] Zero point signal logic reverse 3 3 3 –––– –
M 8347*2 [Y000] Interrupt signal logic reverse 3 3 –––– –
[M]8348 [Y000] Positioning instruction activation 3 3 3 –––– –
M 8349*2 [Y000] Pulse output stop command 3 3 3 –––– –
[M]8350 [Y001] Pulse output monitor
(ON: BUSY/ OFF: READY)
3 3 3 –––– –
M 8351*2 [Y001] Clear signal output function enable 3 3 3 –––– –
M 8352*2 [Y001] Zero return direction specification 3 3 3 –––– –
M 8353 [Y001] Forward limit 3 3 3 –––– –
M 8354 [Y001] Reverse limit 3 3 3 –––– –
M 8355*2 [Y001] DOG signal logic reverse 3 3 3 –––– –
M 8356*2 [Y001] Zero point signal logic reverse 3 3 3 –––– –
M 8357*2 [Y001] Interrupt signal logic reverse 3 3 –––– –
[M]8358 [Y001] Positioning instruction activation 3 3 3 –––– –
M 8359*2 [Y001] Pulse output stop command 3 3 3 –––– –
Timing Clock (Refer to Section 24.3 for details.) and Positioning [FX
3U
and FX
3UC
PLCs] (Refer to Positioning Control Edition for details.)
[M]8360 [Y002] Pulse output monitor
(ON: BUSY/ OFF: READY)
3 3 3 –––– –
M 8361*2 [Y002] Clear signal output function enable 3 3 3 –––– –
M 8362*2 [Y002] Zero return direction specification 3 3 3 –––– –
M 8363 [Y002] Forward limit 3 3 3 –––– –
M 8364 [Y002] Reverse limit 3 3 3 –––– –
M 8365*2 [Y002] DOG signal logic reverse 3 3 3 –––– –
M 8366*2 [Y002] Zero point signal logic reverse 3 3 3 –––– –
M 8367*2 [Y002] Interrupt signal logic reverse 3 3 –––– –
[M]8368 [Y002] Positioning instruction activation 3 3 3 –––– –
M 8369*2 [Y002] Pulse output stop command 3 3 3 –––– –
*1. Available in Ver. 2.20 or later.
*2. Cleared when the PLC switches from RUN to STOP.
*3. Available in the Ver. 1.30 or later.
Number and name Operation and function
Applicable model
FX
3G FX3U
FX
3UC
Correspond-
ing special
device
FX
1S
FX
1N
FX
2N
FX
1NC
FX