846
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
37 Operation of Special Devices (M8000 -, D8000 -)
37.1 Special Device List (M8000 -, D8000 -)
Analog Special Adapter [FX3U, FX3UC] (Refer to Subsection 37.2.19 for applicability of each analog special adapter.)
D 8260 to D 8269 1st special adapter*1 33*2 –––– –
D 8270 to D 8279 2nd special adapter*1 33*2 –––– –
D 8280 to D 8289 3rd special adapter*1 33*2 –––– –
D 8290 to D 8299 4th special adapter*1 33*2 –––– –
Analog Special Adapter, Analog Expansion Board [FX3G]
(Refer to Subsection 37.2.18 for applicability of each analog special adapter.and analog expansion board)
D 8260 to D 8269 1st expansion board*3 3*6 –––– –
D 8270 to D 8279 2nd expansion board*4*5 3*6 –––– –
D 8280 to D 8289 1st special adapter*1 3 –––– –
D 8290 to D 8299 2nd special adapter*1*5 3 –––– –
*1. Count the number of connected analog special adapter from the main unit.
*2. Available in Ver. 1.20 or later.
*3. Expansion board connected to the BD connector of a 14-point or 24-point type main unit or the BD1
connector of a 40-point or 60-point type main unit.
*4. Expansion board connected to the BD2 connector of a 40-point or 60-point type main unit.
*5. Only a 40-point or 60-point type FX3G PLC can be connected.
*6. Available in Ver. 1.10 or later.
Display Module Function (FX3G-5DM, FX3U-7DM) (Refer to Hardware Edition Manual of PLC main unit used for details.)
D 8300 Control device (D) for display module
Default: K-1 3*7 3 3 –––– –
D 8301 Control device (M) for display module
Default: K-1 3*7 3 3 –––– –
D 8302*8
Language display setting
Japanese: K0
English: Other than K0
3*7 3 3 –––– –
D 8303 LCD contrast setting value
Default: K0 3*7 3 3 –––– –
[D]8304
Not used
– – –––– –
[D]8305 – – –––– –
[D]8306 – – –––– –
[D]8307 – – –––– –
[D]8308 – – –––– –
[D]8309 – – –––– –
*7. Available in Ver. 1.10 or later.
*8. Latch (battery or EEPROM backed) device. For details on backup against power failure, refer to Section 2.6.
RND (FNC184)
[D]8310 Lower RND (FNC184) instruction:
Data for generating random number
Default: K1
3 3 –––– –
[D]8311 Upper
Number and name Content of register
Applicable model
FX
3G
FX
3U
FX
3UC
Correspond-
ing special
device
FX
1S
FX
1N
FX
2N
FX
1NC
FX
2NC