PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions
9 One-speed Interrupt constant quantity feed -DVIT Instruction
9.1 Instruction Format
B - 124
3. Devices
1 : Specify Y000, Y001, or Y002 transistor output from the main unit, or specify Y000, Y001, Y002*2, or
Y003*2 from a high-speed output special adapter*1.
*1. A high-speed input/output special adapter cannot be connected to the FX3UC PLC.
*2. To use Y002 and Y003 with a high-speed output special adapter, connect a second high-speed output
special adapter.
Point:
To use an FX3U Series main unit of relay output type, be sure to connect a high-speed output special
adapter. Differential line drive type outputs will be used for the outputs of the high-speed output special
adapter.
2 : When a high-speed output special adapter is used as a destination for pulse output on a FX3U PLC,
use the output shown in the following table for rotation direction signals.
When a built-in transistor output is used as a destination for pulse output on a FX3U/FX3UC PLC, use
transistor output for signals rotation direction.
For the outputs applicable with a High-speed output special adapter, refer to Section 4.9.
3:D.b cannot be indexed by index registers (V and Z).
Operand
type
Bit device Word device Others
System user Digit designation System user Special
unit Index Con-
stant
Real
num-
ber
Char-
acter
string
Pointer
XYMTCSD
.b KnXKnY KnM KnS T C D R U\GV Z Modify K H E ""P
333 3
3333 3333
3 3 3 3 3333 3 3 3 3
13
23333
High-speed output special adapter connection position Pulse output Rotation direction output
1st adapter = Y000 = Y004
= Y001 = Y005
2nd adapter = Y002 = Y006
= Y003 = Y007