(2) Station information setting

 

 

 

 

Setting

Item*1

 

 

Set value

necessity at

 

 

GOT

 

 

 

 

 

 

 

 

connection

Station type

 

 

Intelligent

 

 

device station (fixed)

 

 

 

 

 

 

 

 

Exclusive station count*2

 

Exclusive station 1

 

Reserve/invalid station

 

 

No setting

 

select

 

 

 

 

 

 

 

 

 

 

 

 

Intelligent buffer select

 

(Use default value)

 

(word)

 

 

 

 

 

 

 

 

 

 

 

 

: Necessary

: As necessary

: Not necessary

*1 When the [Mode] of the CC-Link module is set at [Remote net - (Ver. 1 mode)], [Remote station points] cannot be set.

*2 Set the same setting as that of the GOT.

POINT

When changing the network parameter

After writing the network parameter to the PLC CPU, operate the PLC CPU ether turning OFF and then ON or resetting.

13.4.5Connecting to MELSEC-L series with CC-Link Ver.2 compatible

This section describes the settings of the GOT and MELSEC-L in the following case of the system configuration.

POINT

(1)CC-Link module (L Series)

For details of the CC-Link module (L Series), refer to the following manual.

MELSEC-L CC-Link System Master/Local

Module User's Manual

(2)CC-Link function built-in CPU

For details on the CC-Link function built-in CPU, refer to the following manual.

MELSEC-L CC-Link System Master/Local

Module User's Manual

System configuration

(Example when using CC-Link module (L Series))

[Controller Setting] of GT Designer3

<GOT>

(Use the default value for settings other than the following.)

Station type

:

Intelligent device

 

 

station

9

TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)

10

MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

11

CC-Link IE CONTROLLER NETWORK CONNECTION

12

CC-Link IE FIELD NETWORK CONNECTION

13

[Controller Setting] of GT Designer3

Item

Set value

Station No.

1: Station No.1

 

 

Transmission Rate

0: Online 156kbps

 

 

Mode

Ver.1: Remote net (Ver.1 mode)

 

 

Expanded Cyclic

Single (Use default value)

 

 

Number of stations occupied

1 Station

 

 

Input for Error Station

0: Clear

 

 

Retry

3times (Use default value)

 

 

Timeout Time

3sec (Use default value)

 

 

Delay Time

0ms (Use default value)

 

 

POINT

[Controller Setting] of GT Designer3

For the setting method of [Controller Setting] of GT Designer3, refer to the following.

13.3.1 Setting communication interface (Communication settings)

Station No.

Expanded cyclic setting Number of

stations occupied

Transmission speed

<CC-Link module> *1

(Use the default value for the settings other than the following.)

Type

:

Master station

Station No.

:

Station No.0

Mode

:

Remote net (Ver.3 mode)

All connect count

:

1

Transmission speed :

156kbps

[Network parameter] of GX Developer

:Station No.1

:Single

:Exclusive station

:156kbps

CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

14

CC-Link CONNECTION (Via G4)

15

CONNECTION

INVERTER

16

CONNECTION

SERVO AMPLIFIER

13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

13 - 25

13.4 PLC Side Setting