2 Description of Analog Products
2.2 List of Analog Product Models
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
Voltage/current input/output mixture
FX2N-5A*1
Input
4ch
Voltage:
-10V to +10V DC
0.32mV
(with sign, 16 bits) Combined use of voltage and
current is possible.
The offset/gain can be
adjusted.*3
The scaling function is
incorporated.
*2
Current:
-20mA to +20mA DC
1.25μA
(with sign, 15 bits)
Output
1ch
Voltage:
-10V to +10V DC
5mV
(with sign, 12 bits)
Current:
0mA to 20mA DC
20μA
(10bits)
FX0N-3A*1, *4
Input
2ch
Voltage:
0V to 10V DC
40mV
(8bits)
The input format is common to 2
channels.
The offset/gain can be adjusted.
(Common to 2 input channels)
*2
Current:
4mA to 20mA DC
64μA
(8bits)
Output
1ch
Voltage:
0V to 10V DC
40mV
(8bits)
Current:
4mA to 20mA DC
64μA
(8bits)
Temperature sensor input
FX2N-8AD*1 8ch
Type K:
-100°C to +1200°C0.1°CCombined use of voltage,
current, and thermocouple is
possible.
Compatible with thermocouple
types K, J, and T.
The unit can be switched between
"Centigrade" and "Fahrenheit."
The sampling function is
incorporated.
*2
Type J:
-100°C to +600°C0.1°C
Type T:
-100°C to +350°C0.1°C
FX2N-4AD-TC*1 4ch
Type K:
-100°C to +1200°C0.4°CCompatible with thermocouple
types K and J.
The unit can be switched between
"Centigrade" and "Fahrenheit."
*2
Type J:
-100°C to +600°C0.3°C
FX2N-4AD-PT*1 4ch Pt100:
-100°C to +600°C0.2°C to 0.3°C
Compatible with the platinum
resistance thermometer sensor
(Pt100 or JPt100).
The unit can be switched between
"Centigrade" and "Fahrenheit."
*2
FX2N-2LC*1 2ch
Example:
Type K:
-100°C to +1300°C
0.1°C or 1°C
(Depends on the
sensor input range.)
Compatible with thermocouple
types K, J, R, S, E, T, B, N, PL II,
WRe5-26, U, and L.
Compatible with the platinum
resistance thermometer sensor
(Pt100, JPt100).
The unit can be switched between
"Centigrade" and "Fahrenheit."
The temperature adjustment
function (PID operation, etc.) is
incorporated.
The peak disconnection
detection function is
incorporated.
(A CT sensor is needed.)
*2
Pt100:
-200°C to +600°C
*1.To connect this block to the FX3UC Series PLC, either the FX2NC-CNV-I F or FX3UC-1PS-5V is required.
*2.Refer to the instruction manual of the respective product.
*3.The offset and gain of the FX2N-5A cannot be adjusted for channels using the analog value direct
indication mode or analog value mV (or μA) specification mode.
*4.The FX0N-3A cannot be connected to the FX3G Series PLC.
Type No. of
channels Range Resolution Function Refer-
ence